6 Commissioning
Issue 05 (2020-04-07)
Copyright © Huawei Technologies Co., Ltd.
44
6.2 Setting the Display Language
After powering on the SMU, press
or
on the LCD to select a display language. Then
press
to enter the standby screen.
If an undesired language is selected, reinstall and restart the SMU and then select the desired language.
6.3 Setting the Date and Time
The LCD backlight turns off if no button is pressed within 30 seconds.
Re-login is required if no button is pressed within 1 minute.
The preset password for login is
000001
.
Set the date and time as required.
Table 6-1
Setting the date and time
Main Menu
Second-Level
Menu
Third-Level
Menu
Default Value
Settings
Setting Wizard
Date and Time
NOTE
The date and time
vary with time
zones. Set the time
zone, date, and
time based on the
local situation.
Time Zone
UTC +08:00
Beijing
Set to the local time zone.
Date and Time
-
Set to the local date and
time.
NTP Enable
No
Yes/No
NOTE
Set the parameter to
Yes
if you
need to synchronize the SMU
time and the site network server
time.
6.4 Setting Battery Parameters
Set
Battery1 Connected
,
Battery2 Connected
,
Battery3 Connected
,
Battery4 Connected
,
Rated Capacity
,
Installation Time
as required.
Table 6-2
Setting battery parameters
Main Menu
Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Default
Value
Setting
Parameters
Settings
Battery
Basic
Parameters
Battery1
Connected
Yes
Yes/No