ETP48400-C9A2 Embedded Power
User Manual
6 Commissioning
Issue 05 (2020-04-07)
Copyright © Huawei Technologies Co., Ltd.
45
Main Menu
Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Default
Value
Setting
Battery2
Connected
Yes
NOTE
If
N
battery strings
are connected, set
Battery 1 Connected
to
Battery N
Connected
to
Yes
,
and set the other
parameters to
No
.
Battery3
Connected
Yes
Battery4
Connected
Yes
Rated Capacity
150 Ah
Rated capacity of
the batteries in a
battery string.
NOTE
The batteries
connected to one
circuit breaker or fuse
are called a battery
string.
Other
Parameters
Installation Time
-
Set this parameter to
the current date.
If battery routes 1 and 2 are respectively connected to a battery string (each battery string consists of
four 12 V, 150 Ah batteries in series), set
Battery1 Connected
and
Battery2 Connected
to
Yes
and
others to
No
, and set
Rated Capacity
to
150 Ah
.
If battery route 1 is connected to two battery strings in parallel (each battery string consists of four
12 V, 150 Ah batteries in series), set
Battery1 Connected
to
Yes
and others to
No
, and set
Rated
Capacity
to
300 Ah
.
6.5 (Optional) Setting Sensor Parameters
Set sensor parameters based on site requirements.
Table 6-3
Setting sensor parameters
Main Menu
Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Default
Value
Setting
Parameters
Settings
Power System
Sensor Config.
Para
Door sensor
None
Set to
Yes
or
None
based
on site
requirements.
Water sensor
None
Smoke sensor
None
Ambient Temp.
Sensor
None
Ambient Humi.
Sensor
None