6 Commissioning
Issue 05 (2020-04-07)
Copyright © Huawei Technologies Co., Ltd.
46
Main Menu
Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Default
Value
Setting
Batt. Temp. Sensor
1
None
Batt. Temp. Sensor
2
None
6.6 (Optional) Setting the Hibernation Parameter
Set
Hibernation Enable
to
Yes
if you need to use the intelligent hibernation function of the
rectifiers.
Table 6-4
Setting the hibernation parameter
Main Menu
Second-Level
Menu
Third-Level Menu
Default Value
Setting Value
Parameters Settings
Energy Saving
Hibernation Enable
No
Yes
6.7 Setting Communications Parameters
6.7.1 (Optional) Setting Parameters Before Using WebUI
Operating Environment
Supported operating system: Windows XP or later
Browser: Internet Explorer 8.0 or later, FireFox 13 or later, or Chrome 20
Internet Explorer is used as an example to illustrate all WebUI operations mentioned in this document.
Setting a LAN
If the SMU is connected to a LAN and a proxy server has been selected, cancel the proxy
server settings.
If the SMU is connected to the Internet but your computer is connected to a LAN, do not
cancel the proxy server settings. Otherwise, you cannot access the SMU.
To cancel proxy server settings, perform the following steps: