7.1 Routine Maintenance
Perform routine maintenance based on site requirements. The recommended maintenance
interval is six months.
Table 7-1
Routine maintenance checklist
Maintenance
Item
Check Item
Check
Method
Scenario for
Repair
Measures
Electricity
The AC input
voltage is
normal.
Clamp meter
The AC input
voltage is
beyond the
normal range.
For details, see
7.3 Identifying
Component
Faults
The output
voltage is
normal.
The battery
branch or load
branch voltage
exceeds the
specified range
(-42 V DC to
-58 V DC).
Preventive
maintenance
inspection
The indicators
are normal.
Observe
indicators
Alarms are
generated.
Grounding
The ground
point properly
connects to the
ground bar in
the cabinet.
Clamp meter
The resistance
between the
ground point
and the ground
bar is greater
than 0.1 ohm.
Secure the
ground cable to
the ground
point again or
replace the
ground cable.