4 Installation
Issue 05 (2020-04-07)
Copyright © Huawei Technologies Co., Ltd.
36
Figure 4-10
Connecting a communications cable (over SNMP)
(1) User SNMP terminal
(2) FE port on the SMU
----End
4.7 Installing DC Output Power Cables
Prerequisites
Ensure that the upstream AC input circuit breaker is OFF, and attach labels such as "No
operations allowed."
Switch off all circuit breakers before installing power cables.
Procedure
Step 1
Remove the front panel of the DC PDU.
Step 2
Route DC output power cables through the protective board on the top of the subrack.
Step 3
Secure the negative DC output power cable to the corresponding DC output circuit breaker
based on the actual load.
Step 4
Connect the positive DC output power cable to the corresponding screw on the RTN+ busbar.