CA UTION
● As the fire cylinder is heavy, determine the installation position, port, and
fastening mode in advance to avoid long-distance movement.
● Do not impact or strike the fire cylinder during transportation or installation.
Do not remove or flip the dowel on the fire cylinder.
● Assign at least four persons for transportation and installation if no auxiliary
tool is available.
● After the fire cylinder is installed, do not remove the safety pin on the fire
cylinder. Instead, remove the safety pin only after the fire extinguishing system
starts working properly.
● Do not touch any button in the fire extinguishing system without permission
during installation.
● Do not power on the fire extinguishing system during installation.
Preparations
Tools: flat-head screwdriver, pallet truck, adjustable wrench, pipe wrench, step
ladder, protective gloves
Materials: fire cylinder, high-pressure hose, sealing tape, threaded adapter, I-
shaped connector
Skill requirement: common technician
Procedure
Step 1 Move the fire cylinder using a pallet truck to a position near the pre-fab. module
door closest to the installation position.
NO TICE
Do not move the fire cylinder over a long distance by hands.
Step 2 Untie the preconfigured steel straps at the installation position of the fire cylinder.
Step 3 Move the fire cylinder to the installation position and secure it.
NO TICE
Keep the pressure gauge panel outwards so that people can view the reading,
which also facilitates later maintenance.
FusionDC1000A Prefabricated All-in-One Data
Center
Installation Guide (IT Scenario)
8 Installing Devices Inside the Pre-fab. Module
Issue 01 (2021-04-20)
Copyright © Huawei Technologies Co., Ltd.
86