FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
6 Parts Replacement
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
100
Figure 6-18
Connecting the signal cable and extension cable
Step 6
Check that the new water sensor is working properly.
Dip the water detection cable into water. If the monitoring software terminal generates an alarm, the
water sensor is working properly.
----End
Follow-up Procedure
Dispose of the removed water sensor that is confirmed faulty.
6.3.4 Replacing a Door Status Sensor
Prerequisites
A door status sensor needs to be replaced.
A spare door status sensor of the same model is available and functional.
Impact on the System
None
Preparations
Tools: insulation tape, step ladder (2 m), Phillips screwdriver, small-sized flat-head
screwdriver, protective gloves
Materials: spare door status sensor
Documents: monitoring device layout, management system initial configuration table
Skill requirement: weak-current engineer
For the diagrams and tables, see the initial configuration parameter manual for the solution in use.
Procedure
Step 1
Open the container door where the door status sensor to be replaced is installed.