FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
6 Parts Replacement
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
130
Figure 6-46
Heat detector installation reference line
Step 7
Power on the fire alarm control panel after verifying that the new heat detector is properly
installed.
Step 8
Check whether the new heat detector is working properly.
If the red indicator blinks once every 6s, the heat detector is working properly.
----End
Follow-up Procedure
Dispose of the removed heat detector that is confirmed faulty.
6.4.3 Replacing the Gas Release Indicator (Standard)
Prerequisites
A gas release indicator needs to be replaced.
A spare gas release indicator of the same model is available and functional.
Impact on the System
The fire extinguishing system stops working during the replacement.
Preparations
Tools: Phillips screwdriver, protective gloves, step ladder, flat-head screwdriver
Materials: spare gas release indicator
Documents: fire extinguishing device layout diagram (standard)
Skill requirement: fire engineer