FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
6 Parts Replacement
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
142
Figure 6-58
Connecting battery cables
Distinguish the positive and negative battery terminals when connecting battery cables.
Step 6
Use a Phillips screwdriver to secure the battery fixing plate.
Figure 6-59
Securing the fixing plate
Step 7
Switch on the standby power supply to the fire alarm control panel.
Step 8
Check that the new batteries are working properly.
If the
BATTERY FAULT
indicator on the fire alarm control panel is off, the new batteries are working
properly.
----End
Follow-up Procedure
Dispose of the removed fire alarm control panel batteries that are confirmed faulty.