FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
6 Parts Replacement
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
176
Figure 6-93
Removing the extinguishant control panel
Step 6
Install the new extinguishant control panel in the same position.
Step 7
Put the corrugated pipes and cables back to the box, and reconnect the cables according to
labels.
Step 8
Put the batteries to the same position.
Step 9
Switch on the input circuit breaker of the extinguishant control panel, and connect the battery
cables.
Step 10
Check whether the new extinguishant control panel is working properly.
If the power indicator is on and the alarm indicator is off, the fire control panel is working properly.
----End
Follow-up Procedure
Dispose of the removed extinguishant control panel that is confirmed faulty.
6.5.11 Replacing an Emergency Light (CE)
Prerequisites
An emergency light needs to be replaced.
A spare emergency light of the same model is available and functional.
Impact on the System
None