FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
4 Routine Maintenance
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
21
4.2 Routine Maintenance
Table 4-2
Routine maintenance checklist
Categ
ory
Item
Method
Expected
Result
Troubleshooting
Manag
ement
system
FusionMo
dule1000
alarms
Choose
Fault
>
Current Alarms
or
Fault
>
Historical
Alarms
on the
home page of the
management
system.
No alarm is
displayed in the
alarm
information
area.
See the iManager NetEco
product documents.
Alarm short
messages can be
received.
Check whether the GSM
modem is properly
connected. If the GSM
modem is faulty, replace it
by following instructions in
Camera
images
and
coverage
Choose
Camera
>
Camera
>
Camera
Management
,
right-click a
camera name on
the right side, and
view the video
images captured
by the camera.
The video
images are
properly
displayed.
If no video image is
displayed:
1.
Connect the camera
cable again.
2.
If the cable is correctly
connected, replace the
camera by following
instructions in
If the camera is normal but
no video image is
displayed:
1.
Connect the VCN500
cable again.
2.
If the cable is correctly
connected, replace the
camera by following
instructions in
The coverage of
the camera is
optimal.
If the camera coverage does
not meet the monitoring
requirement, adjust the
camera coverage.
Access
controller
communi
cation
status
Check the door
status list in the
management
system, and
verify whether
the access
controller is
working
After
configuring the
access controller
in the
management
system, you can
check the access
controller
If a door status icon is
dimmed (unavailable),
check the access controller
and network status.