FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
4 Routine Maintenance
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
27
Item
Method
Expected
Result
Troubleshooting
misshapen.
Check electric
heaters.
The electric
heaters and
switches are
secure.
Secure the electric heaters and
switches.
The electric
heater surface
is not
corroded.
Replace the faulty electric heater by
following instructions in the air
conditioner user manual.
Check the
temperature-humid
ity sensor.
Check that T/H
sensors in the
air conditioner
and aisles are
securely
installed.
Secure the T/H sensor.
Check the water
sensor.
The water
sensor is
secure, and the
two downward
metal
conductive
plates do not
touch with
each other and
are free from
corrosion.
Replace the faulty water sensor by
following instructions in the air
conditioner user manual.
Thermal
insulation
foam for
the
humidifier/
condensate
drainpipe
Check whether the
thermal insulation
layers are in good
condition without
condensation.
The thermal
insulation
layers are in
good condition
and free from
condensation.
If there is condensate water under
the pipe, replace by following
instructions in
4.3.3 Monitoring System
When you check the hydrogen sensor in the container, only a small amount of hydrogen needs
to be released onto the sensor. During the entire process, flames and sparks are prohibited in
or around the power supply and battery compartments.