FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
4 Routine Maintenance
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
44
Item
Method
Expected
Result
Troubleshooting
when the
container
door is
closed.
Press down the
button after
removing the glass
cover of the
emergency door
release button.
The container
door can be
opened.
If the container door cannot be
opened, replace by following
instructions in
an Emergency Door Release Button
Press the exit
button and open
the door.
The door can
be opened.
1.
Check whether the cable to the
exit button is properly
connected.
2.
If the fault persists, replace by
following instructions in
Swipe a card to
open the door.
When an
access card is
swiped, the
card reader
indicator
blinks green
once and then
returns to
steady red.
You will hear
a beep.
Swipe another access card and
observe the door status:
If the door can be opened by
another access card, the original
access card is damaged. Prepare
a new access card and assign
permission to the card.
If the door cannot be opened,
replace by following instructions
in
(Optional) Read
your fingerprint to
open the door after
your fingerprint
has been collected
and assigned the
access permission.
The container
door can be
opened.
If the container door cannot be
opened, replace by following
instructions in
Check the
mechanical lock.
The
mechanical
lock is free
from rust or
corrosion.
If the mechanical lock is rusty or
corroded and affects door opening,
contact Huawei technical support.
Hydrogen
detection
system
Check whether the
hydrogen collector
has generated
alarms.
The hydrogen
collector is
working
properly, and
no alarm is
generated.
Troubleshoot by following
instructions in documents delivered
with the hydrogen collector.
Check the LCD of
the hydrogen
The LCD
displays the
1.
Check that the AC input power
cable is normal.