FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
6 Parts Replacement
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
98
Figure 6-15
Removing a point-type water sensor
Step 3
Install a new water sensor and tighten the screws.
Step 4
Connect cables to the water sensor.
Step 5
Check that the new water sensor is working properly.
Drip a small amount of water onto the water sensor. If the monitoring software terminal generates an
alarm, the water sensor is working properly.
----End
Follow-up Procedure
Dispose of the removed water sensor that is confirmed faulty.
6.3.3 Replacing a Water Sensor (Rope Type)
Prerequisites
A water sensor needs to be replaced.
Spare water sensors of the same model are available and functional.
Impact on the System
None
Preparations
Tools: Phillips screwdriver, protective gloves
Materials: spare water temperature sensor
Documents: monitoring device layout, management system initial configuration table
Skill requirement: weak-current engineer