FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
6 Parts Replacement
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
128
Figure 6-44
Smoke detector installation reference line
Step 7
Power on the fire alarm control panel after verifying that the new smoke detector is properly
installed.
Step 8
Check whether the new smoke detector is working properly.
If the red indicator blinks once every 6s, the smoke detector is working properly.
----End
Follow-up Procedure
Dispose of the removed smoke detector that is confirmed faulty.
6.4.2 Replacing a Heat detector (Standard)
Prerequisites
A heat detector needs to be replaced.
A spare heat detector of the same model is available and functional.
Impact on the System
The fire extinguishing system stops working during the replacement.
Preparations
Tools: protective gloves, step ladder, Phillips screwdriver
Materials: spare heat detector
Documents: fire extinguishing device layout diagram (standard)
Skill requirement: fire engineer