FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
7 Emergency Operations
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
191
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.
7.12 Emergency Operations for a Double Fire Alarm
(Standard)
Prerequisites
The management system reports a double fire alarm.
The following double fire alarm emergency operations are for reference only.
If a double fire alarm is generated, determine whether to extinguish the fire or leave the
area immediately based on the actual situation and contact the personnel on duty or fire
engineer.
Procedure
Step 1
Locate the alarm or alarm area in the management system.
Step 2
Check the internal situation in the video surveillance system.
If the video surveillance system indicates that everything is normal, go to
If onsite fire is confirmed, go to
Step 3
Check whether extinguishant has been released.
If extinguishant is being released, contact the local maintenance engineer or Huawei
technical support to recharge the extinguishant after the fire has been extinguished.
If no extinguishant is released, check the situation onsite, and contact the fire engineer.
Step 4
Arrive at the site with necessary tools and communications devices as soon as possible, open
the external fire control box, and press the
EMERGENT RELEASE
on the fire alarm
control panel.