FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
7 Emergency Operations
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
193
7.13 FIRE RELAY Emergency Operations (CE)
Prerequisites
The management system reports a FIRE RELAY alarm.
The following FIRE RELAY emergency operations are for reference only.
If a FIRE RELAY alarm is generated, determine whether to extinguish the fire or leave the
area immediately based on the actual situation and contact the personnel on duty or fire
engineer.
Procedure
Step 1
Locate the alarm area based on the alarm information.
Step 2
Check the internal situation in the video surveillance system.
If the video surveillance system indicates that everything is normal, go to
If onsite fire is confirmed, go to
Step 3
Check whether extinguishant has been released.
If extinguishant is being released, contact the local maintenance engineer or Huawei
technical support to recharge the extinguishant after the fire has been extinguished.
If no extinguishant is released, check the situation onsite, and contact the fire engineer.
Step 4
Take necessary tools and communications devices, arrive at the site as soon as possible, and
press the manual gas release button on the extinguishant control panel to start releasing
extinguishant.