FusionModule1000A20 Prefabricated All-in-One Data
Center
Maintenance Guide
3 Routine Maintenance
Issue 01 (2019-07-15)
Copyright © Huawei Technologies Co., Ltd.
13
3.2 Routine Maintenance
Table 3-2
Routine maintenance checklist
Category
Maintenance
Item
Instructions
Criteria
Troubleshooti
ng
ECC800
WebUI
FusionModule1
000A alarms
On the ECC800
WebUI, choose
Home
>
Active
Alarms
or
Query
>
Historical
Alarms
.
No alarm is
displayed in the
alarm
information
area.
Clear the alarm
by referring to
the ECC800
documents.
Alarm short
message service
(SMS)
messages can
be received.
Check whether
the SIM card is
properly
installed.
Replace the
SIM card if it is
faulty.
Camera images
and angles
On the ECC800
WebUI, choose
System
>
Video
Settings
>
Video
Information
.
Click
Access
Link
to display
the linked video
page.
The video
images are
properly
displayed.
If no video
image is
displayed:
1.
Connect the
camera
cable again.
2.
If the cable
is properly
connected,
replace the
camera.
The coverage of
the camera is
optimal.
If camera
angles do not
meet the
monitoring
requirement,
adjust them by
following the
instructions in
the
commissioning
guide.
Fire
extinguishing
system
VESDA and its
power supply
Check the
working status
of the VESDA
and its power
supply.
The VESDA
and its power
supply are
normal.
If the VESDA
or its power
supply is
abnormal,
troubleshoot by
following
instructions in
documents
delivered with
the VESDA.