Install a new exit button and reconnect cables.
Step 3
Check whether the new exit button is working properly.
If the pre-fab. module door can be opened using the exit button, and the door opening event is logged,
the new exit button is working properly.
----End
4.3.6.3 Replacing a Magnetic Lock
Prerequisites
A spare magnetic lock of the same model is available and functional.
Impact on the System
None
Preparations
Tools: Phillips screwdriver, 3 mm hex key, step ladder (2 m)
Material: spare magnetic lock
Documents: none
Skill requirement: ELV engineer
Procedure
Step 1
Use a Phillips screwdriver to loosen screws from the baffle plate of the magnetic lock, as
shown by (1) in Figure 4-19.