FusionModule1000A20 Prefabricated All-in-One Data
Center
Maintenance Guide
3 Routine Maintenance
Issue 01 (2019-07-15)
Copyright © Huawei Technologies Co., Ltd.
14
3.3 Monthly Maintenance
3.3.1 Power Supply and Distribution System
Table 3-3
Monthly maintenance checklist for the power supply and distribution system
Maintenance
Item
Instructions
Criteria
Troubleshooting
Check the luminance of
the indicators.
The three-phase
power indicators
are bright.
Replace the indicator.
Check the SPD
indicator and SPD
circuit breaker status.
The SPD indicator
is green.
If the SPD indicator is red, replace the SPD.
The SPD circuit
breaker is switched
to ON.
Switch on the circuit breaker.
3.3.2 Surveillance system
Table 3-4
Monthly maintenance checklist for the surveillance system
Check Item
Description
Criteria
Troubleshooting
Access actuator
Power input
Input voltage: 36–60 V
DC
Check the input power
cables if the input voltage
is abnormal.
PWR indicator
Steady on: The power
supply is normal.
Off: No power supply is
available.
Check the input power
cables.
ALM indicator
Steady on: A fault alarm
is raised.
Off: No fault alarm is
raised.
Clear the alarm by
referring to the ECC800
documents.
RUN indicator
Off: The power supply is
abnormal.
Blinking slowly: The
registration with the
ECC800 is successful or
the software runs
properly (the indicator
blinks at 0.5 Hz, on for 1s
Check the power supply.
If the RUN indicator
blinks fast, check whether
the communications cable
is normal. If not, replace
the cable.