FusionModule1000A20 Prefabricated All-in-One Data
Center
Maintenance Guide
4 Parts Replacement
Issue 01 (2019-07-15)
Copyright © Huawei Technologies Co., Ltd.
56
Preparations
Tools: ESD wrist strap, ESD gloves, label, marker
Materials: new pad of the same model
Documents: none
Skill requirement: extra low voltage (ELV) engineer
Procedure
Step 1
Install the app on the spare pad and connect the pad to the network over the WiFi hotspot of
the data center.
Step 2
Specify the user name and password for the APP on the spare pad and log in to check that the
app works properly.
Step 3
Remove the old pad from the support and install the spare pad on the support.
----End
4.4 Replacing Fire Extinguishing System Components (CE)
4.4.1 Replacing a Smoke Detector (CE)
Prerequisites
A spare smoke detector of the same model is available and functional.
Impact on the System
The fire extinguishing system stops working during the replacement.
Preparations
Tools: protective gloves, step ladder, Phillips screwdriver
Materials: spare smoke detector
Document: fire extinguishing device layout diagram (CE)
Skill requirement: fire engineer