FusionModule1000A20 Prefabricated All-in-One Data
Center
Maintenance Guide
4 Parts Replacement
Issue 01 (2019-07-15)
Copyright © Huawei Technologies Co., Ltd.
74
Figure 4-39
Removing the extinguishant control panel
Step 6
Install the new extinguishant control panel in the same position.
Step 7
Put the corrugated pipes and cables back to the box, and reconnect the cables according to
labels.
Step 8
Put the batteries to the same position.
Step 9
Switch on the input circuit breaker of the extinguishant control panel, and connect the battery
cables.
Step 10
Check whether the new extinguishant control panel is working properly.
If the power indicator is on and the alarm indicator is off, the fire control panel is working properly.
----End
4.4.11 Replacing an Emergency Light (CE)
Prerequisites
A spare emergency light of the same model is available and functional.
Impact on the System
None
Preparations
Tools: Phillips screwdriver, flat-head screwdriver, step ladder, protective gloves
Materials: spare emergency light
Documents: none