FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
3 Maintenance
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
12
Item
Method
Expected
Result
Troubleshooting
The refrigerant
pipe support is
secure and
intact.
If the pipe support is worn out or
not properly fixed, replace and
tighten the support by following
instructions in
NetCol5000-A 20 kW
Air-Cooled In-Row Precision Air
Conditioner User Manual
.
Thermal
insulation
foam on the
humidifier/
condensate
drainpipe
Check the thermal
insulation foam.
The thermal
insulation
foam is in
good condition
and free from
condensation.
If there is condensation under a
pipe, replace the thermal insulation
foam.
3.2.3 Monitoring System
Table 3-4
Monthly maintenance checklist for the monitoring system
Item
Method
Expected
Result
Troubleshooting
Event and
operation
logs in the
RH2288
server
Choose System
Event Log in the
navigation tree.
Normal system
events are
displayed.
If a system event exception is found,
troubleshoot by referring to
documents delivered with the
RH2288 server.
ECC500
collector
Check the
indicators of the
ECC500 main
control module.
The running
indicator is
steady on.
If the running indicator blinks at
short intervals, check that power
supply of the ECC500 collector
is normal, and check that the
communications cable between
the ECC500 and the host is
properly connected.
If the alarm indicator is on, view
and handle the alarms.
VCN500
indicator
Check the
VCN500 indicator.
The VCN500
indicator is
steady green.
If the indicator is in an abnormal
status, troubleshoot by following
instructions in
VCN500 Product
Documentation
.