FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
3 Maintenance
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
15
Device
Operation
Check
Standard
Troubleshooting
Unplug the input
power supply.
The
emergency
light turns on,
the power
indicator turns
off, and the
fault indicator
turns off.
Replace the emergency light.
Smoke
detector
Check the smoke
detector indicator.
The indicator
blinks once
every 6s.
Replace the smoke detector.
Heat
detector
Check the heat
detector indicator.
The indicator
blinks once
every 6s.
Replace the heat detector.
3.2.5 Fire Extinguishing System (CE Kidde)
Table 3-6
Monthly maintenance checklist for the fire extinguishing system
Device
Operation
Check
Standard
Troubleshooting
Extinguisha
nt control
panel
Check indicators
on the
extinguishant
control panel.
The power
indicator turns
on, and the
alarm indicator
turns off.
Replace the extinguishant control
panel.
Extinguisha
nt control
panel
batteries
Check the battery
terminals.
The wiring
terminals are
in good
condition
without
corrosion.
Clean the contaminated and
corroded terminals. Replace the
batteries with severely corroded
terminals for the fire alarm control
panel..
Fire
extinguishe
r
Check the
appearance of the
fire cylinder,
electric control
head, pressure
operated switch,
fire extinguishing
pipeline, and
nozzle.
All devices of
the fire
extinguisher
are intact, free
from
deformation
and
mechanical
damage.
Replace the fire cylinder. For details
about how to replace other devices,
contact Huawei technical support.