Maintenance Item Operation
Check Standard
Troubleshooting
Screws securing the
indoor fan of the 20
kW air-cooled
precision air
conditioner
Check screws
securing the indoor
fan.
The indoor fan
screws are secure.
If an indoor fan
screw is loose,
tighten the screw.
Air filters of the 20
kW air-cooled
precision air
conditioners
Check the air filters.
The filters are clean
and not blocked.
If an air filter is dirty
or blocked, remove
dust from the air
filter using a brush
or vacuum cleaner.
The air filters are
not damaged or
misshapen.
Replace any
damaged or
misshapen air filters
for a 20 kW
air-cooled precision
air conditioner.
Condensate pan and
floats of the 20 kW
air-cooled precision
air conditioner
Check the
condensate pan and
floats.
The condensate pan
and floats are free
from scale.
If there is scale on
the condensate pan
and floats, clean the
condensate pan and
floats.