FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
3 Maintenance
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
34
Device
Operation
Check
Standard
Troubleshooting
If the
temperature
exceeds the
alarm
threshold, the
gas release
indicator turns
on. The fire
alarm control
panel
generates an
alarm and
triggers the fire
alarm sounder.
Replace the heat detector if the fault
persists.
Smoke
detector
Release smoke
onto the smoke
detector using a
smoke pistol.
If the smoke
density is
below the
alarm
threshold, the
alarm indicator
blinks once
every 6s.
Replace the smoke detector
If the smoke
density
exceeds the
alarm
threshold, the
indicator turns
on. The fire
alarm control
panel
generates an
alarm and
triggers the fire
alarm sounder.
Replace the smoke detector if the
fault persists.
Fire alarm
horn/strobe
Unlock the fire
alarm control panel
and press
HORN/STROBE
.
The fire alarm
horn/strobe
generates
glaring flashes
and shrill
alarms.
1.
Check cables connected to the
fire alarm control panel. If a
short circuit or open circuit is
identified, reconnect the cables.
2.
Replace the indoor fire alarm
horn/strobe if the fire alarm
horn/strobe does not react.
3.4.5 Fire Extinguishing System (CE Kidde)