FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
3 Maintenance
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
35
Semi-annual maintenance of the fire extinguishing system involves system commissioning.
Before the maintenance, inform the related administrative departments that the fire
extinguishing system will be maintained and stop working.
Before maintaining the fire extinguishing system, remove the electric control head from
the container valve of the fire cylinder. This prevents the extinguishant release due to
misoperations, and prevents accidental damage.
After the maintenance, reconnect the electric control head to the container valve of the fire
cylinder, and inform the administrative departments that the fire extinguishing system has
become operational.
Table 3-20
Semi-annual maintenance checklist for the fire extinguishing system
Device
Operation
Check Standard
Troubleshooting
Fire
extinguishi
ng system
commission
ing
Commission the
fire extinguishing
system by
following the
instructions in the
Fire
Extinguishing
System
Commissioning
(CE)
section in the
commissioning
guide for the
solution in use.
Devices work
properly, and the
management system
displays related
alarms.
Replace the fire extinguishing
system components (CE).
Heat
detector
Heat the heat
detector using a
heating device.
1.
If the
temperature is
below the alarm
threshold, the
heat detector
indicator is off.
2.
If the
temperature is
above the alarm
threshold, the
heat detector
indicator turns
on. The
extinguishant
control panel
reports a loop 1
FIRE RELAY,
and the buzzer
buzzes.
Replace the heat detector.