FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
4 Alarms and Faults
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
62
Fault
Category
Alarm
Severity
Symptom
Possible
Cause
Troubleshooti
ng
Check the
compressor
power supply
status. If the
power supply is
faulty, check
whether the
power cable is
abnormal, and
whether the
compressor
power supply
circuit breaker
is off or
abnormal. If a
fault is
identified,
rectify the fault
and check
whether the
abnormality
disappears.
The compressor
is damaged.
Replace the
compressor by
following
instructions in
NetCol5000-A
20 kW
Air-Cooled
In-Row
Precision Air
Conditioner
User Manual
Major
The compressor
generates a loud
noise.
The sheet metal
for securing the
compressor
during
transportation is
not removed.
Remove the
sheet metal and
check whether
the abnormality
disappears.