FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
5 Components Replacement
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
72
Procedure
Step 1
Switch off the circuit breaker of the faulty rPDU in the PDC.
Step 2
Remove all power connectors from the rPDU.
Step 3
Remove the baffle plate from the top of the cabinet using a Phillips screwdriver.
Step 4
Remove the rPDU power cable on the top of the cabinet.
Step 5
Use a Phillips screwdriver to remove the screws that secure the rPDU support from the upper
and lower parts of the rPDU front panel.
Figure 5-4
Removing screws at the upper and lower parts of the rPDU
Step 6
Lift the faulty rPDU and take it out.
Step 7
Remove the support and screws from the faulty rPDU and install them on a new rPDU.
Step 8
Mount the new rPDU with a support into the cabinet, and tighten the fastening screws of the
rPDU using a Phillips screwdriver.