FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
5 Components Replacement
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
80
Step 8
Choose
Maint
>
Performance Maint
on the home screen and clear the air filter running
time.
----End
Follow-up Procedure
Dispose of the removed air filter that is confirmed faulty.
5.2.4 Replacing a Ventilation Vent Air Filter
Prerequisites
An air filter needs to be replaced.
A spare air filter of the same model is available and functional.
Impact on the System
None
Preparations
Tool: flat-head screwdriver, step ladder, brush
Materials: spare air filters
Document: none
Skill requirement: cooling engineer
Procedure
Step 1
Remove the air filter using a flat-head screwdriver.
Figure 5-10
Removing an air filter
Step 2
Clear foreign matter inside the ventilation vent using the brush.
Step 3
Install the spare air filter.
----End