5 Components Replacement
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
120
Figure 5-45
Securing the fixing plate
Step 7
Switch on the standby power supply to the fire alarm control panel.
Step 8
Check that the new batteries are working properly.
If the
BATTERY FAULT
indicator on the fire alarm control panel is off, the new batteries are working
properly.
----End
Follow-up Procedure
Dispose of the removed fire alarm control panel batteries that are confirmed faulty.
5.4.8 Replacing a Fire Cylinder (Standard)
Prerequisites
A spare fire cylinder of the same model is available and functional.
Impact on the System
The fire extinguishing system stops working during the replacement.
Preparations
Tools: pallet truck, Phillips screwdriver, protective gloves, adjustable wrench
Materials: spare fire cylinder, sealing tape
Documents: fire extinguishing device layout diagram (standard)
Skill requirement: fire engineer