FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
3 Maintenance
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8
3
Maintenance
3.1 Routine Maintenance
Table 3-1
Routine maintenance checklist
Cate
gory
Item
Method
Expected
Result
Troubleshooting
Mana
geme
nt
syste
m
FusionMo
dule1000
alarms
Choose
Alarm
>
Current Alarms
on the home page
of the
management
system to view
alarms.
No alarm is
displayed in the
alarm
information area.
If an alarm is displayed in
the alarm information area,
perform the following
operations:
1.
Clear the alarm by
following instructions in
iManager NetEco
Product Document -
(NetEco Version)
.
2.
Check whether cables are
connected properly and
rectify faults.
Camera
images
and
coverage
Choose
Configuration
>
Camera
Management
>
Video Camera
Management
,
right-click a
camera name on
the right side, and
view the video
images captured
by the camera.
You can view
the video
images.
If no video image is
displayed:
1.
Connect the camera cable
again.
2.
If the cable is correctly
connected, replace the
camera.
If the camera is normal but
no video image is displayed:
1.
Connect the VCN500
cable again.
2.
If the cable is correctly
connected, replace the
VCN500.