6 Emergency Operations
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
179
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.
6.4 Emergency Operations for Overtemperature
Prerequisites
The FusionModule1000 is experiencing overtemperature or an overtemperature alarm is
generated.
Procedure
Step 1
Locate the high-temperature area.
Step 2
Measure the actual ambient temperature using a thermometer.
Step 3
Check whether the actual temperature exceeds the designed normal range.
If no, replace the remote T/H sensor for an air conditioner.
If yes, go to
Step 4
Lower the temperature in the area.
Step 5
Refer to the section "Temperature Alarms."
----End
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.
6.5 Emergency Operations for the Management System
Communication Failure
Prerequisites
The management system communication is interrupted.
Before the management system communication is restored, the management system cannot
perform real-time monitoring for the FusionModule1000 data center. Add people to perform
preventive maintenance inspection in related areas.