FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
3 Maintenance
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
26
3.3.5 Fire Extinguishing System (CE Kidde)
Table 3-13
Quarterly maintenance checklist for the fire extinguishing system
Item
Operation
Check
Standard
Troubleshooting
Extinguisha
nt control
panel
batteries
1.
Switch off the
power input
circuit breaker
of the
extinguishant
control panel so
that the
batteries power
the panel.
2.
Measure the
battery voltage
using a
multimeter.
1.
The
extinguisha
nt control
panel
reports a
power
supply
fault.
2.
The battery
voltage is
24±1 V
DC.
Replace batteries for the
extinguishant control panel.
Hand-held
fire
extinguishe
r
Check the
hand-held fire
extinguisher.
The hand-held
fire
extinguisher is
in good
condition.
Replace the hand-held fire
extinguisher.
The pressure
pointer of the
hand-held fire
extinguisher is
in the green
zone.
Replace the hand-held fire
extinguisher.
The hand-held
fire
extinguisher is
within the
validity period.
Replace the hand-held fire
extinguisher.
3.3.6 Fire Extinguishing System (CE Tyco)
Table 3-14
Quarterly maintenance checklist for the fire extinguishing system
Device
Operation
Check Standard
Maintenance Guide