Device
Operation
Check Standard
Maintenance Guide
Extinguisha
nt control
panel
batteries
1.
Switch off the
power input
circuit breaker
of the fire alarm
control panel so
that the
batteries power
the panel.
2.
Measure the
battery voltage
using a
multimeter.
1.
The extinguishant
control panel reports a
power supply fault.
2.
The battery voltage is
24±1 V DC.
Replace batteries for
the extinguishant
control panel.
Hand-held
fire
extinguishe
r
Check the
hand-held fire
extinguisher.
The hand-held fire
extinguisher is in good
condition.
Replace the hand-held
fire extinguisher.
The pressure pointer of the
hand-held fire extinguisher
is in the green zone.
The hand-held fire
extinguisher is within the
validity period.
3.3.7 Other Systems
Table 3-15
Quarterly maintenance checklist for other systems
Item
Method
Expected
Result
Troubleshooting
Pre-fab.
module
body
Check the pre-fab.
module.
The pre-fab.
module body is
clean.
If the pre-fab. module body is not
clean:
1.
Clean the pre-fab. module using
a long-handled soft brush and
alkaline or neutral detergent.
2.
Wash the pre-fab. module with
clean water.
Pre-fab.
module
paint
Check the
appearance of the
pre-fab. module.
The pre-fab.
module and
bases are free
from paint
flake-off, rust,
or corrosion.
If any part has paint flake-off, rust,
or signs of other corrosion, maintain
or replace the corroded or damaged
part.