3.4 Semi-annual Maintenance
3.4.1 Power Supply and Distribution System
Table 3-16
Semi-annual maintenance checklist for the power supply and distribution system
Item
Method
Expected
Result
Troubleshooting
Circuit
breaker
labels of the
PDC and
UPS
Check the circuit
breaker labels.
The circuit
breaker labels
are legible and
intact.
If a circuit breaker label is blurry,
replace the label.
ATS
controller
LCD
Check the ATS
controller LCD.
The LCD is
on.
If the LCD does not light up:
1.
Check and reconnect the power
cable.
2.
Replace the ATS by following
instructions in documents
delivered with the ATS.
The display
panel of the
controller
displays
information
properly.
If the display is abnormal (vague or
no display):
1.
Check and reconnect the power
cable.
2.
Replace the ATS by following
instructions in documents
delivered with the ATS.
3.4.2 Cooling System
Table 3-17
Semi-annual maintenance checklist for the cooling system
Item
Method
Expected Result Troubleshooting
Pipes
Check the safety
clamps of the
pipes.
Nuts on safety
clamps are secure.
If a safety clamp nut is loose,
tighten it using a hex key.
Switches
and fuses
inside the
electric
control box
Check the switches
and fuses.
All circuit
breakers and fuses
work properly.
If a switch or fuse is abnormal,
replace it.
Cable
connections
inside the
electric
control box
Check the cable
connections inside
the electric control
box.
Cables are
securely
connected.
If a cable is loose, reconnect is