Fault
Category
Alar
m
Sever
ity
Symptom
Possible
Cause
Troubleshooting
PD510
communic
ation
failure
Major
Real-time
monitoring cannot be
performed.
Cables are not
properly
connected.
Verify the cable
connections.
Powered on the power
distribution equipment
where the electricity
meter is installed again.
The device is
faulty.
Replace the PD510
electricity meter.
Managem
ent system
communic
ation
failure
Critica
l
Real-time
monitoring cannot be
performed.
The
FusionModule1
000 is powered
off or the circuit
breaker has
tripped.
Refer to the section
"Emergency Operations
for the Management
System Communication
Failure" or "Emergency
Operations for Circuit
Breaker Tripping."
VCN500
communic
ation
failure
Major
Real-time
monitoring cannot be
performed.
Cables are not
properly
connected.
Verify the cable
connections.
The device is
faulty.
Replace the VCN500.
ECC500
communic
ation
failure
Major
Real-time
monitoring cannot be
performed.
Cables are not
properly
connected.
Verify the cable
connections.
The device is
faulty.
Replace the ECC500
collector.
4.15 SPD Alarm
Fault
Category
Alar
m
Sever
ity
Symptom
Possible
Cause
Troubleshooting
SPD
alarm
Warni
ng
The SPD module
indicator is red.
The SPD
module is
damaged by a
lightning strike.
Replace the SPD in a
PDC.