FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
4 Alarms and Faults
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
60
Fault
Category
Alarm
Severity
Symptom Possible Cause
Troubleshootin
g
Major
Abnormal
noise or
smell is
generated
in the UPS
cabinet.
The UPS is faulty. Shut down the
UPS and cut off
the power input
immediately.
Contact Huawei
technical support.
Major
The battery
indicator
blinks. The
buzzer
buzzes. The
battery
capacity is
insufficient,
and the
UPS is
shutting
down.
The UPS will
soon shut down
due to low
battery, and loads
will be powered
off.
Save data and
shut down
primary loads
immediately to
avoid data loss or
corruption.
Connect the UPS
input to the
backup AC power
supply
immediately.
The number of
batteries or the
battery capacity is
incorrectly set.
Verify that the
number of
batteries and
battery capacity
are correctly set
based on the
actual
configuration, and
that the settings
are consistent
with the initial
configuration
requirements in
UPS2000-G-(6
kVA-20 kVA)
User Manual
and
the initial
configuration
parameter
manual.
For other UPS2000-G alarms, see
UPS2000-G-(6 kVA-20 kVA) User Manual
.
4.18 20 kW Air-Cooled Precision Air Conditioner Alarms
Fault
Category
Alarm
Severity
Symptom
Possible
Cause
Troubleshooti
ng