5 Components Replacement
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
70
Step 6
Reinstall the protective panel.
Step 7
Check that the new SPD is working properly.
----End
Follow-up Procedure
Dispose of the removed SPD module that is confirmed faulty.
5.1.3 Replacing a Monitoring rPDU
Prerequisites
A monitoring rack power distribution unit (rPDU) needs to be replaced.
A spare monitoring rPDU of the same model is available and functional.
Impact on the System
None
Preparations
Tools: Phillips screwdriver, protective gloves
Materials: spare monitoring rPDU
Document: none
Skill requirement: electrician's work permit
Procedure
Step 1
Shut down devices powered by the monitoring rPDU.
Step 2
Switch off the circuit breaker of the monitoring rPDU, and unplug devices powered by the
rPDU.
Step 3
Disconnect the male connector of the monitoring rPDU from its female connector.
Step 4
Remove the monitoring rPDU using a Phillips screwdriver.