5 Components Replacement
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
73
Figure 5-5
Installing screws at the upper and lower parts of the rPDU
Step 9
Connect the rPDU power cable on the top of the cabinet.
Step 10
Switch on the circuit breaker for the rPDU in the PDC and check that the new rPDU is
working properly.
Step 11
Insert device power plugs in the rPDU.
Step 12
Reinstall the cabinet top baffle plate.
----End
Follow-up Procedure
Dispose of the removed rPDU that is confirmed faulty.
5.1.5 Replacing a Light (Standard)
Prerequisites
Before replacement, disconnect the light power switch to avoid live-line working.
Context
A light can be installed on the ceiling. There is a PC plate under a ceiling-mounted light.
Move the PC plate away when replacing the light.