10
Installing Monitoring Devices
10.1
Installing the SIM Card and Antenna
1. Remove the ECC800-Pro main control module.
2. Install the SIM card.
3. Attach the antenna to the middle of the cabinet top.
4. Connect the antenna cable.
10.2
Installing a PAD
1. Adjust the PAD mounting support to match the dimensions of the PAD to be installed.
2. Remove the nuts from the PAD mounting support and install the support.
3. Route the PAD power cable through the cable hole and connect the cable.
4. Clamp the PAD.
5. Connect the ECC800-Pro USB cable to the charging port on the PAD.
Adjusting
screws
12
10.3
Installing T/H Sensors
1. Unpack the two T/H sensors, and attach
one to the 33 U position on the right
post of the front door and the other to
the 3–4 U position on the right post of
the rear door of the cabinet.
2. Set the DIP switch address of the T/H
sensor on the front door to 2 and that of
the T/H sensor on the rear door to 1.
•
The installation positions of the T/H sensors can be adjusted as required.
•
The default device address is 1.
Installing Remote T/H Sensors for
Smart Cooling Products
Installing Cabinet T/H Sensors
1. Unpack the two T/H sensors and attach
one sensor to the mounting bars at the
40th U position on the front door and the
other to the 34th U position on the rear
door of the cabinet
2. Set the DIP switch address of the T/H
sensor on the front door to 2 and that of
the T/H sensor on the rear door to 1.