26
3.11
Commissioning Linkage Control
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose
System Settings
>
Linkage Control
.
3. Ensure that
Enable linkage control function
is set to
Yes
.
4. On the
Linkage Group
tab page, set
Link smoke alarm with clasp lock open
to
on
.
5. Modify the AI/DI_1 signal name.
6. Enable the AI/DI device.
Unlocking the Cabinet Electronic Clasp Lock When a Smoke Alarm Is Generated
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose
System Settings
>
Linkage Control
.
3. Ensure that
Enable linkage control function
is set to
Yes
.
4. On the
Linkage Group
tab page, set
Link fire control with clasp lock open
to
on
.
5. Modify the AI/DI_3 signal name.
6. Enable the AI/DI device.
Unlocking the Cabinet Electronic Clasp Lock When a Fire Alarm Is Generated
Setting Parameters on the Client
1. Install the VCN IVS client in the VCN scenario. Install the iClient in the IVS1800 scenario..
2. Add a camera. For details, see the documentation delivered with the equipment or obtain the
documentation by referring to the "Preparing Documentation" section. View the
corresponding section.
3. Configure a video recording plan.
4. Create a user.
Setting Parameters on the VCN or IVS1800 WebUI
1. Logging In to the OMU Portal.
2. Initializing Hard Disks.
3. Modify the IP address for the VCN or IVS1800.
4. Enable camera NTP synchronization.
•
For details about the VCN or IVS1800 hardware description and installation, see the
"Hardware Guide" in the corresponding VCN or IVS1800 product documentation. For details
about the VCN or IVS1800 configuration, see
Configuration Guide.
•
VCN commissioning description: The VCN510-8 and VCN510-16P need to be distinguished.
The default user name of the VCN510-8 is Admin, and the default user name of the
VCN510-16P is admin. The default passwords of them are Change_Me. Their parameter
settings on the WebUI are different. For details, see the Commissioning Guide.