FusionModule1000A40 Prefabricated All-in-One Data
Center
Installation Guide
8 Installing Devices Inside Pre-fab. Modules
Issue 03 (2020-06-09)
Copyright © Huawei Technologies Co., Ltd.
66
Step 3
Install cable terminals on the iBAT, and ensure that there are no gaps at the cable terminal
connections.
Figure 8-20
Connecting an iBAT
----End
8.4 Installing Fire Extinguishing Devices
8.4.1 Installing CE-Certified Fire Extinguishing Devices
8.4.1.1 (Optional) Installing the Fire Cylinder (CE)
Prerequisites
The pre-fab. modules have been installed.
The extinguishant in the fire cylinder meets the requirement.
As the fire cylinder is heavy, determine the installation position, port, and fastening mode
in advance to avoid long-distance movement.
Do not impact or strike the fire cylinder during transportation or installation. Do not
remove or flip the dowel on the fire cylinder.
Assign at least four persons for transportation and installation if no auxiliary tool is
available.
Do not touch any button in the fire extinguishing system without permission during
installation.
Do not power on the fire extinguishing system during installation.
Preparations
Tools: protective gloves, pallet truck, pipe wrench, adjustable wrench, step ladder