FusionModule1000A40 ICT Solution
Maintenance Guide
3 Routine Maintenance
Issue 01 (2019-03-05)
Copyright © Huawei Technologies Co., Ltd.
22
Check
Item
Operation
Check Standard
Troubleshooting
RF_Z
indicator
On: No network
parameters exist. A
network is waiting
to be created.
Blinking slowly: A
network is set up,
and node access is
not allowed (the
indicator blinks at
0.5 Hz, on for 1s
and then off for 1s).
Blinking at super
short intervals: A
network is set up,
and node access is
allowed (the
indicator blinks at
10 Hz, on for 0.05s
and then off for
0.05s).
Blinking at super
short intervals
intermittently: The
device is searching
for a network (the
indicator blinks at 2
Hz, on for 0.5 and
then off for 0.5s).
Refer to
ECC800 Data Center
Controller V100R001C30 User
Manual
to register the device, or
contact Huawei technical support.
Pad
Exterior
The exterior is
intact and the
touchscreen is
working properly.
Replace the pad.
Exit button
Function
The function is
normal.
Replace by following instructions in
4.3.11.2 Replacing an Exit Button.
3.5.4 Fire Extinguishing System (Standard)
Table 3-7
Monthly maintenance checklist for the fire extinguishing system
Device
Operation
Check
Standard
Troubleshooting
Fire alarm
control
panel
Check indicators
on the fire alarm
control panel.
The power
indicator turns
on, and the
alarm indicator
turns off.
Replace by following instructions in
4.4.1.10 Replacing a Fire Alarm
Control Panel (Standard).