Figure 4-55 Installing fasteners
NO TICE
When laying out the water detection cable, ensure that the water detector is close
to the cabinet to facilitate further cable connections.
Step 6 Place the water detection cable onto the fastener, secure the fastener, and keep
the water detection cable in close contact with the floor, as shown in
Figure 4-56 Securing a water detection cable
NO TE
If multiple water detection cables are connected in series, connect the male connector of
one cable to the female connector of another.
----End
4.2.6.6 Installing an Electrode Water Sensor
If the water sensor is required, perform the following steps to install it.
Procedure
Step 1 Place the water sensor on the floor under the cabinet.
Step 2 Route the water sensor cable through the cable hole in the lower cover of the
cabinet.
Step 3 Connect it to the water sensor cable connected to the ECC.