1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add a rack-mounted HR04A.
Table 5-1 Adding a smart cooling product (rack-mounted HR04A)
Path
Parameter
Setting
Choose
System
Settings >
Device
Management
and click Add
Device. The
parameters
for adding a
device are
displayed.
Device
attribute
Select Air Conditioner from the drop-
down list box.
Device Type
Select Rack-mounted air conditioner
HR04A from the drop-down list box.
Connect To
Select ECC800 from the drop-down list
box.
Communicati
ons Port
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the rack-
mounted HR04A is connected to the COM3 port
on the ECC800. If the HR04A is connected to
another port, enter the number of the
connected port.
Device
Address
Enter the actual device address of the rack-
mounted HR04A during operations. The
default address is 1.
3. Click Test Connect to check whether the rack-mounted HR04A is properly
connected to the ECC800-Pro.
–
If the connection is normal, click Confirm. The connected devices are
displayed in the Number of connected devices list.
–
If the connection is abnormal, check whether the device is properly
connected to the ECC800-Pro, whether the device and the ECC800-Pro are
running properly, and whether the parameter settings are consistent with
the device parameters.
Step 2 Set the running parameters and control parameters of the rack-mounted HR04A
on the WebUI.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose Monitoring > Cooling > Rack-mounted air conditioner HR04A1.
3. On the Running Parameters tab page, set smart cooling product running
parameters.
NO TE
You are advised to set Supply air temperature settings to 20°C, Return air
temperature settings to 30°C, and Dehumidification settings to 50% RH.
4. On the Controls tab page, set the smart cooling product control parameters
(such as on/off control parameters).
FusionModule500 Smart Mini Data Center
User Manual
5 Power-On Commissioning
Issue 02 (2020-12-25)
Copyright © Huawei Technologies Co., Ltd.
157