Figure 5-7 Adding a device
----End
5.3.6 Creating a Micro-module Plan View
Procedure
Step 1 Choose Home > Plan View, create a micro-module in Micro-Module View and
set the layout and device quantity based on the actual micro-module scenario.
Step 2 Drag the icons of registered devices and devices on the cabinet list to appropriate
positions in the layout to create a micro-module plan view.
----End
5.3.7 Adding a UPS2000G
Prerequisites
One end of the straight-through cable has been connected to the RS485 port on
the UPS2000G, and the other end has been connected to the COM4 port on the
ECC800-Pro.
Procedure
Step 1 Add a UPS2000G-L.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add a UPS2000G-L.
Table 5-5 Adding a UPS2000G-L
Path
Parameter
Setting
Choose
System
Settings >
Device
Management
and click Add
Device. The
parameters
for adding
Device
attribute
Select UPS from the drop-down list box.
Device Type
Select UPS2000G-L from the drop-down
list box.
Connect To
Select ECC800 from the drop-down list
box.
FusionModule500 Smart Mini Data Center
User Manual
5 Power-On Commissioning
Issue 02 (2020-12-25)
Copyright © Huawei Technologies Co., Ltd.
170