Maintenance
Area
Maintenance
Item
Operation
Expected Result Troubleshootin
g
Cleanliness
-
Wipe the cabinet
surface using a
white paper and
the paper does
not turn black.
Remove the
dust, especially
from the air
filter on the
front door, or
replace the air
filter.
Parameter
configuration
-
The
configuration of
the output
voltage grade,
frequency,
number of
batteries, and
battery capacity
meets
requirements.
Reset the
parameters.
Power cables and
terminals
(between the UPS
and the power
distribution
subrack)
-
The insulation
layer of cables is
intact and
terminals are
free from
noticeable
sparks.
● Replace
damaged
cables.
● Secure
output
terminals.
Lithium battery
Battery
management
alarm
-
No battery
management
alarm is
generated.
Identify the
cause of an
alarm based on
the alarm
information.