Maintenance
Area
Maintenance
Item
Operation
Expected Result Troubleshootin
g
UPS
Operating
environment
-
● Ambient
temperature:
0–40°C
● Humidity:
0%–95% RH
(non-
condensing)
● If the
temperature
or humidity
is abnormal,
check the
smart
cooling
product
status.
● If the input
voltage is
abnormal,
check the
power grid
status and
input cable
connection.
LCD
-
According to the
status icons on
the LCD, all units
are operating
properly. No
fault or alarm
information is
found in the
active and
historical alarm
records.
If an alarm is
present, rectify
the fault by
checking the
device status
and parameters.
Cleanliness
-
Wipe the cabinet
surface using a
white paper and
the paper does
not turn black.
Remove the
dust, especially
from the air
filter on the
front door, or
replace the air
filter.
Parameter
configuration
-
The
configuration of
the output
voltage grade,
frequency,
number of
batteries, and
battery capacity
meets
requirements.
Reset the
parameters.
FusionModule500 Smart Mini Data Center
User Manual
6 O&M