background image

NO TICE

Wrap the exposed cable with insulation tape.

Step 4 Remove screws from the UPS front panel, and pull out the UPS.

Step 5 Install the new UPS and screw it to the cabinet.

Step 6 Connect the output power cables, signal cable, and UPS input power cables in

sequence. Check whether the cable labels are consistent with the silk screens on

the UPS, and whether all cables are connected.

Step 7 Switch on the external battery circuit breaker to start the UPS. You can set the

battery capacity based on the site requirements.

Step 8 Press and hold ON/MUTE for more than 5s. Release the button when you hear a

beep sound. The UPS starts to work in normal mode.

Step 9 After you ensure that the UPS runs properly, switch on the AC output circuit

breaker Q for the UPS to start the load.

----End

6.4.2.4 Replacing a Lithium Battery

Prerequisites

Tools: insulation gloves, Phillips screwdriver, socket wrench

Material: A new battery module is intact.

The gyroscope function is disabled.

NO TICE

Before the replacement, ensure that the load services are not affected or obtain

written consent from the customer.

Procedure

Step 1 Switch the BAT– battery circuit breaker on the power system to OFF or remove the

battery fuse.

Step 2 Use the Manual ON/OFF button on the battery to turn off the battery output.

Step 3 Disconnect the cables from the old battery. Insulate each cable and label it

immediately after disconnecting it.

Step 4 Loosen the screws on the panel and remove the battery.

Step 5 Install the new battery and tighten the screws.

Step 6 Hold down the Manual ON/OFF button for 15s for the battery to enter the

maintenance mode. In this mode, all indicators blink, the battery board is

activated, but the battery is not charged or discharged.

FusionModule500 Smart Mini Data Center

User Manual

6 O&M

Issue 02 (2020-12-25)

Copyright © Huawei Technologies Co., Ltd.

271

Summary of Contents for FusionModule500

Page 1: ...FusionModule500 Smart Mini Data Center V100R021C00 User Manual Issue 02 Date 2020 12 25 HUAWEI TECHNOLOGIES CO LTD ...

Page 2: ...s document may not be within the purchase scope or the usage scope Unless otherwise specified in the contract all statements information and recommendations in this document are provided AS IS without warranties guarantees or representations of any kind either express or implied The information in this document is subject to change without notice Every effort has been made in the preparation of th...

Page 3: ...l of risk which if not avoided will result in death or serious injury Indicates a hazard with a medium level of risk which if not avoided could result in death or serious injury Indicates a hazard with a low level of risk which if not avoided could result in minor or moderate injury Indicates a potentially hazardous situation which if not avoided could result in equipment damage data loss performa...

Page 4: ...es between document issues are cumulative The latest document issue contains all updates made in previous issues Issue 02 2020 12 25 Added information about IVS1800 overview installation commissioning and maintenance Issue 01 2020 10 28 This issue is the first official release FusionModule500 Smart Mini Data Center User Manual About This Document Issue 02 2020 12 25 Copyright Huawei Technologies C...

Page 5: ...arios 18 2 3 2 Typical Configurations 18 3 System Architecture 20 3 1 Structural System 20 3 2 Power Supply and Distribution System 21 3 2 1 Overview 21 3 2 2 6 kVA UPS 22 3 2 3 Power Distribution Subrack 23 3 2 4 Optional rPDU 24 3 2 5 Lithium Battery ESM 48100B1 24 3 3 Cooling System 25 3 3 1 Application Conditions 25 3 3 2 Technical Specifications 26 3 4 Management System 27 3 4 1 Overview 27 3...

Page 6: ...nt Data Center Management System 53 3 4 4 1 System Overview 53 3 4 4 2 Server 54 3 4 4 3 LAN Switch 54 3 5 Surge Protection and Grounding System 55 3 5 1 Surge Protection Solution 55 3 5 2 Grounding Solution 55 3 6 Cable Management 56 4 Installation Guide 57 4 1 Installation Preparations 57 4 1 1 Tools and Instruments 57 4 1 2 Installation Environment Check 60 4 1 3 Site Equipment Preparation 61 4...

Page 7: ...0 Water Sensor 110 4 2 6 6 Installing an Electrode Water Sensor 112 4 2 6 7 Optional Installing a Server 113 4 2 6 8 Optional Installing a Camera 115 4 2 6 9 Optional Installing a LAN Switch 119 4 2 6 10 Optional Installing a VCN510 120 4 2 6 11 Optional Installing an IVS1800 126 4 3 Cable Routing 131 4 3 1 System Cabling Rules 132 4 3 2 Grounding the Smart Module 136 4 3 3 Cable Connections to th...

Page 8: ...r Sensor 174 5 3 8 4 Commissioning the Electrode Water Sensor 175 5 3 9 Commissioning a Cabinet Electronic Clasp Lock 176 5 3 10 Configuring Event Notification 180 5 3 11 Video Management 185 5 3 11 1 Preparing Documentation 185 5 3 11 2 Networking Scenario 186 5 3 11 3 Commissioning Cameras LAN Switch Networking Scenario 186 5 3 11 3 1 Commissioning a C3220 Camera 186 5 3 11 3 2 Commissioning a C...

Page 9: ...EDCM Communication Parameters on the ECC800 Pro 230 5 3 13 2 7 Connecting to the Network 231 6 O M 234 6 1 Routine Maintenance 234 6 1 1 Monthly Maintenance 234 6 1 2 Quarterly Maintenance 240 6 1 3 Yearly Maintenance 247 6 2 Troubleshooting 257 6 2 1 Power Supply and Distribution System Troubleshooting 257 6 2 2 Management System Troubleshooting 260 6 3 Alarm References 262 6 4 Parts Replacement ...

Page 10: ... 4 3 9 Replacing a T H Sensor 33010516 283 6 4 3 10 Replacing a Smoke Detector 284 6 4 3 11 Replacing a WLDS900 Water Sensor and Water Detection Rope 285 6 4 3 12 Replacing an Electrode Water Sensor 288 7 Technical Specifications 289 A Equipment Derating Coefficients 290 B Acronyms and Abbreviations 291 FusionModule500 Smart Mini Data Center User Manual Contents Issue 02 2020 12 25 Copyright Huawe...

Page 11: ... warranty Follow local laws and regulations when installing operating or maintaining the equipment The safety instructions in this document are only supplements to local laws and regulations Huawei will not be liable for any consequences of the following circumstances Operation beyond the conditions specified in this document Installation or use in environments which are not specified in relevant ...

Page 12: ...for installation operation and maintenance Before handling a conductor surface or terminal measure the contact point voltage and ensure that there is no risk of electric shock After installing the equipment remove idle packing materials such as cartons foam plastics and cable ties from the equipment area In the case of a fire immediately leave the building or the equipment area and turn on the fir...

Page 13: ...atches caused during equipment transportation or installation in a timely manner Equipment with scratches cannot be exposed to an outdoor environment for a long period of time Before operations ensure that the equipment is firmly secured to the floor or other solid objects such as a wall or an installation rack Do not use water to clean electrical components inside or outside of a cabinet Do not c...

Page 14: ...ipment Professionals personnel who are trained or experienced in equipment operations and are clear of the sources and degree of various potential hazards in equipment installation operation maintenance Trained personnel personnel who are technically trained have required experience are aware of possible hazards on themselves in certain operations and are able to take protective measures to minimi...

Page 15: ... powered facilities must be performed by qualified personnel Cabling When routing cables ensure that a distance of at least 30 mm exists between the cables and heat generating components or areas This prevents damage to the insulation layer of the cables Do not route cables behind the air intake and exhaust vents of the equipment Ensure that cables meet the VW 1 or ZB flame spread rating requireme...

Page 16: ...with ESD packaging materials before storing or transporting them Figure 1 1 Wearing an ESD wrist strap Neutral Ground Voltage It is recommended that the three phase loads be equalized and the neutral ground voltage be kept at less than 2 V to meet power distribution requirements 1 4 Installation Environment Requirements To prevent fire due to high temperature ensure that the ventilation vents or h...

Page 17: ...ng at heights Wear personal protective equipment such as the safety helmet and safety belt or waist rope and fasten it to a solid structure Do not mount it on an insecure moveable object or metal object with sharp edges Make sure that the hooks will not slide off Set a restricted area and eye catching signs for working at heights to warn away irrelevant personnel Carry the operation machinery and ...

Page 18: ...e wooden or fiberglass ladders when you need to perform live working at heights When a step ladder is used ensure that the pull ropes are secured and the ladder is held firm Before using a ladder check that it is intact and confirm its load bearing capacity Do not overload it Ensure that the ladder is securely positioned The recommended angle for a ladder against the floor is 75 degrees as shown i...

Page 19: ...ents or cables inside Metal shavings from drilling may short circuit boards inside the equipment Obtain the consent from the customer and subcontractor before drilling Wear goggles and protective gloves when drilling holes When drilling holes protect the equipment from shavings After drilling clean up any shavings that have accumulated inside or outside the equipment Moving Heavy Objects DANGER Wh...

Page 20: ... Cooling System Safety Welding At least two persons are required on a welding site A welder must have a work permit A welding site must be free from inflammables Ensure that a fire extinguisher wet wiper and water container are available A burning welding torch must not be placed on a component or on the floor and must not be placed in a metal container with acetylene and oxygen Otherwise the gas ...

Page 21: ...precautions for battery handling and master the correct battery connection methods DANGER Do not expose batteries at high temperatures or around heat generating devices such as sunlight fire sources transformers and heaters Excessive heat exposure may cause the batteries to explode Do not burn batteries Otherwise the batteries may explode To avoid leakage overheating fire or explosions do not disa...

Page 22: ...frared radiation organic solvents and corrosive gases Take fire prevention measures Place and secure batteries horizontally Note the polarities when installing batteries Do not short circuit the positive and negative poles of the same battery or battery string Otherwise the battery may be short circuited Check battery connections periodically ensuring that all bolts are securely tightened When ins...

Page 23: ...tery The safety precautions for lithium batteries are similar to those for lead acid batteries except that you also need to note the precautions described in this section WARNING There is a risk of explosion if a battery is replaced with an incorrect model A battery can be replaced only with a battery of the same or similar model recommended by the manufacturer When handling a lithium battery do n...

Page 24: ...00 Doing so may affect the power supply to equipment which will interrupt services Exercise caution when manually shutting down the UPS inverter for transferring to bypass mode or when adjusting the UPS output voltage level or frequency Doing so may affect the power supply to equipment Exercise caution when setting battery parameters Incorrect settings will affect the power supply and battery life...

Page 25: ...lexibly expanded The FusionModule500 is positioned as a smart module solution and occupies about 10 m2 It is mainly used in the equipment rooms of county level governments bank business outlets and small and medium sized enterprises FusionModule500 Smart Mini Data Center User Manual 2 Overview Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 15 ...

Page 26: ...onModule500 in the financial industry 1 FusionModule5000 2 FusionModule2000 3 FusionModule800 4 FusionModule500 FusionModule500 Smart Mini Data Center User Manual 2 Overview Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 16 ...

Page 27: ...nd integrated cabling system to provide a comprehensive solution High Safety and Reliability The Converged Cabinet incorporates the UPS monitoring system and power distribution system that are designed in modular manner and feature high security and reliability The powerful monitoring system allows you to master the infrastructure status anytime and improves the protection capability of cabinets F...

Page 28: ...nitor the functional modules Provides a pad to easily manage the functional modules locally 2 3 Typical Application Scenarios and Configurations 2 3 1 Typical Scenarios The smart module is mainly used in the equipment rooms of bank business outlets small and medium sized enterprises and governments 2 3 2 Typical Configurations Figure 2 3 Converged Cabinet FusionModule500 Smart Mini Data Center Use...

Page 29: ...minutes Power distribution UPS2000 G lithium battery and rPDU Monitoring ECC800 Pro temperature and humidity T H sensor smoke detector water sensor PAD intelligent lock WiFi converter optional and NetEco optional FusionModule500 Smart Mini Data Center User Manual 2 Overview Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 19 ...

Page 30: ...led on a base which needs to be prepared by customers The cabinet can house ICT devices with a depth of no more than 750 mm Table 3 1 Cabinet technical specifications Item Specifications Color Black Material High intensity class A carbon cold rolled steel plate and zinc coated steel plate Air channel Cold aisle containment Installation mode Installed on a concrete floor or electrostatic discharge ...

Page 31: ...tible power to IT loads by means of lithium batteries when the external power supply fails Figure 3 1 Power distribution principles in the UPS scenario FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 21 ...

Page 32: ...485 communications ports connect to northbound devices 7 USB porta 8 AC input and output terminals behind the cover 9 Battery input terminal behind the cover 10 Parallel current equalization port 11 Emergency power off EPO port 12 Parallel communication ports 13 Battery PE terminal FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Issue 02 2020 12 25 Copyright Huawei Technol...

Page 33: ...t power factor 0 99 Output power factor 0 9 Rated input voltage 220 V AC 230 V AC 240 V AC Input voltage range 110 280 V AC 176 V AC derated 110 V AC 50 load Rated input frequency 50 Hz 60 Hz Input frequency range 50 Hz 46 54 Hz 60 Hz 56 64 Hz Output frequency range 50 Hz 0 5 Peak efficiency Normal mode 93 online mode Normal mode 90 Dimensions H x W x D 131 mm x 438 mm x 480 mm Weight 15 kg 3 2 3 ...

Page 34: ... 3 4 rPDU technical specifications Item Specifications Vertically Installed Half Height rPDU Rated current 32 A Input frequency 50 Hz 60 Hz Input port Cord end terminal no input cable Output port configuration IEC 9 x C13 3 x C19 China standard 9 x 10 A 3 x 16 A Rated output current 32 A 3 2 5 Lithium Battery ESM 48100B1 Lithium batteries provide backup power When the mains is normal the UPS charg...

Page 35: ...urrent 100 A 100 A 35 C The actual charge current depends on the UPS charge capability Maximum charge discharge power 4800 W Installation mode Rack mounted 3 3 Cooling System 3 3 1 Application Conditions Operating Environment Table 3 6 Operating environment Item Split Type Air Conditioner Operating temperature Indoor unit 0 45 C Outdoor unit 20 C to 45 C FusionModule500 Smart Mini Data Center User...

Page 36: ...m outdoor unit placed higher Maximum equivalent length of the one way pipe 60 m If the length exceeds 60 m contact the local customer service center 3 3 2 Technical Specifications Table 3 8 Technical specifications Item Split Type Air Conditioner Power system 220 240 V AC 50 Hz 1 phase Refrigerant R410A Cooling capacity 3 5 kWa Fan type EC fan Air supply mode Front air supply and rear air return D...

Page 37: ...des a module level PAD for local intelligent management in terms of real time monitoring status browsing alarm management and system configuration The NetEco can manage the infrastructures of a single data center or of data centers in various areas in a centralized manner The ECC800 Pro manages the real time status alarms and configuration information about the devices inside the smart module It a...

Page 38: ...lance Connects to three cameras and provides PoE power supply accesses real time video images on the WebUI and invokes historical monitoring data 3 4 2 2 App View Generates a 2 5D layout view that matches the actual layout of the smart module including the power distribution module smart cooling product and T H sensor In addition the resource usage rate of electric energy displayed only when the i...

Page 39: ... Control Supports the linkage logic of aisle smoke alarms or high temperature alarms By default the cabinet doors are opened through linkage by default NOTE The aisle smoke sensor alarm cannot trigger the customer s fire extinguishing system Only dry contact alarm signals are provided If the protected area of the fire extinguishing system is in the smart module when a smoke alarm is generated the ...

Page 40: ...emperature decreases by 1 C for each additional 200 m Table 3 10 ECC800 Pro structural specifications Item Specifications Dimensions L x W x H 442 mm x 330 mm x 43 6 mm Weight 6 3 kg with a single power module and a main control module Color Black Installation requirements Can be installed in a 1 U space in a standard 19 inch cabinet Environmental protection RoHS5 REACH WEEE FusionModule500 Smart ...

Page 41: ...UTPUT2 Table 3 11 provides the power port pin definitions Table 3 11 Power port pin definitions Port Type Pin sequence Description AC Pin1 L Pin2 PE Pin3 N DC Pin1 48V Pin2 48VGND 3 4 3 1 2 Main Control Module Figure 3 8 ECC800 Pro collector main control module 1 USB 2 Status indicator 3 AIDI_1 4 AIDI_2 FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Issue 02 2020 12 25 Co...

Page 42: ... input Rated voltage 200 240 V AC Rated frequency 50 60 Hz Power output Output voltage 42 58 V DC rated voltage 53 5 V DC Output power of two power module supplies 2000 W 200 240 V AC 940 W linear derating at 85 175 V AC Output power of a single power module supply 1000 W 200 240 V AC 470 W linear derating at 85 175 V AC WAN port Supports two WAN ports WAN1 is used to connect to the management sys...

Page 43: ...ensors water sensors and NTC sensors AIDI_1 to AIDI_3 are full function AIDI ports and AIDI_4 to AIDI_5 are simplified AIDI ports without type identification The power supply can be switched on or off and is on by default DO expansion RJ45 Output voltage 13 15 V DC rated voltage 14 5 V DC Supports one active DO port The power supply can be switched on or off and is on by default Fault isolation Th...

Page 44: ... limitation of the wireless module China Telecom SIM cards are not supported USB Supports USB 2 0 and 5 V 1 A power supply After installing the WiFi module connect the WiFi module to the ECC800 Pro using the app on the mobile phone or tablet computer to view the basic information about the smart module such as layout resources energy efficiency environment and alarms You can insert a USB flash dri...

Page 45: ...ommunications ports Figure 3 10 shows the pins of the RJ45 port Figure 3 10 RJ45 port pins There are four GE ports that is two WAN ports WAN1 and WAN2 and two LAN ports LAN1 POE and LAN2 POE Table 3 15 GE port pin definitions Item Description Pin sequence Pin1 GE1 Pin2 GE1 Pin3 GE2 Pin4 GE3 Pin5 GE3 Pin6 GE2 Pin7 GE4 Pin8 GE4 Indicator Green indicator Linked steady on FusionModule500 Smart Mini Da...

Page 46: ...ator Steady on The 12 V DC output is normal Off No 12 V DC output is provided Table 3 17 COM3 12V port pin definitions Item Description Pin sequence Pin1 RS485 Pin2 RS485 Pin3 12V DC_OUT Pin4 RS485 Pin5 RS485 Pin6 Pin7 Pin8 GND Indicator Green indicator Power output indicator Steady on The 12 V DC output is normal Off No 12 V DC output is provided FusionModule500 Smart Mini Data Center User Manual...

Page 47: ...sensors 4 20 mA Pin 6 and Pin 7 can detect the output status of passive dry contact type sensors Pin 3 and Pin 7 can detect temperature sensors Table 3 19 AIDI_1 AIDI_2 and AIDI_3 ports pin definitions Item Description Pin sequence Pin1 Type_1 Pin2 Type_2 Pin3 12V DC Pin4 Type_3 Pin5 Type_4 Pin6 DI Pin7 DI Pin8 GND Indicator Green indicator Power output indicator Steady on The 12 V DC output is no...

Page 48: ... 21 USB port pin definitions Item Description Pin sequence Pin1 5V Pin2 DM Pin3 DP Pin4 GND Indicators Table 3 22 Indicators on the ECC800 Pro main control module Indica tor Color Name Status Description RUN Green Running status indicator Steady on The power supply is normal the program is being loaded Off The power supply is abnormal FusionModule500 Smart Mini Data Center User Manual 3 System Arc...

Page 49: ...r short intervals A network is set up and node access is allowed the indicator blinks at 10 Hz on for 0 05s and then off for 0 05s SW Button Table 3 23 SW button description Function Description Operation Description Indicator Status Wireless network RF_Z 802 15 4 pairing In non wireless network 802 15 4 pairing mode press and hold down the button for 3s to 5s to enter the wireless network pairing...

Page 50: ...rter has no power input or is faulty Blinking at long intervals The converter is being queried the indicator blinks at 0 5 Hz on for 1s and then off for 1s Blinking at short intervals The converter application program is being loaded the indicator blinks at 4 Hz on for 0 125s and then off for 0 125s Yellow Alarm indicator Steady on The converter generates a forewarning indicating that power will b...

Page 51: ...ed Fault indicator Steady on The converter locks out due to output overvoltage The converter delivers no output due to internal faults Off The converter is working properly 3 4 3 2 Environment Monitoring System 3 4 3 2 1 WLDS900 Water Sensor The WLDS900 water sensor with the BOM number of 33010352 consists of a water detection cable a water detector and a conversion cable FusionModule500 Smart Min...

Page 52: ...n cable Table 3 25 WLDS900 water sensor specifications Item Specification Operating voltage 12 V DC 9 16 V DC Operating temperature 20 C to 70 C Storage temperature 40 C to 85 C Humidity 10 80 RH non condensing 3 4 3 2 2 Electrode Water Sensor The electrode water sensor with the BOM number of 33010444 contains electrode probes and cables FusionModule500 Smart Mini Data Center User Manual 3 System ...

Page 53: ... Storage temperature 40 C to 80 C 3 4 3 2 3 T H Sensor Figure 3 13 Appearance The T H sensor uses an RJ45 connector NOTE The appearance of the T H sensor depends on the onsite delivery Figure 3 14 Pins of an RJ45 connector FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 43 ...

Page 54: ...accuracy 1 C Humidity measuring range 5 95 RH Humidity precision 5 RH 25 C 20 80 RH Operating temperature 20 C to 70 C Operating voltage 9 16 V DC Storage temperature 40 C to 70 C Output RS485 3 4 3 2 4 Smoke Detector A smoke detector detects smoke around cabinets Figure 3 15 Smoke detector FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Issue 02 2020 12 25 Copyright Huawe...

Page 55: ...o Management System 3 4 3 3 1 Optional Camera The C3220 camera is a two megapixel infrared zoom dome camera that can be ceiling mounted Figure 3 16 C3220 camera Table 3 30 C3220 camera technical specifications Item Specifications Image sensor 1 2 7 two megapixel progressive scan CMOS Minimum illumination Color 0 002 lux F1 2 AGC ON 1 30s shutter speed Black White 0 0005 lux F1 2 AGC ON 1 30s shutt...

Page 56: ...0p up to 160 Mbit s access bandwidth 64 channel 1080p up to 320 Mbit s access bandwidth Up to 160 Mbit s access bandwidth with intelligent services enabled Video transfer 16 channel 1080p up to 160 Mbit s forwarding bandwidth 64 channel 1080p up to 320 Mbit s forwarding bandwidth Up to 160 Mbit s forwarding bandwidth with intelligent services enabled Playbac k Downlo ad 16 channel 1080p up to 80 M...

Page 57: ...r Processor Hi3559A Memory 8 GB DDR4 External ports Network port Two 10 100 1000 Mbit s Ethernet ports USB ports Three USB ports two USB 2 0 ports on the front panel and one USB 3 0 port on the rear panel Audio input 1 channel RCA port Audio output 1 channel RCA port Alarm port 4 channel alarm input 2 channel alarm output Other specificatio ns Power consumpti on 8 hard disks included 124 W Power s...

Page 58: ...rding bandwidth Video playback and download Supports a maximum of eight video playback and download channels or 128 Mbit s video playback and download bandwidth Ingress and egress bandwidth The ingress bandwidth does not exceed 128 Mbit s The egress bandwidth does not exceed 256 Mbit s Table 3 34 Hardware specifications Item Specifications Number of disks 2 Whether the hard disk supports hot swap ...

Page 59: ...ard disks 60 W Dimensions H x W x D 43 6 mm x 442 mm x 310 mm 1 U excluding the panel 43 6 mm x 442 mm x 320 mm 1 U including the panel 3 4 3 4 Cabinet Electronic Clasp Lock The cabinet electronic clasp lock is used to manage access control It can be automatically unlocked or manually locked and unlocked Figure 3 19 Cabinet electronic clasp lock 1 LED indicator 2 DIP switch 3 RJ45 power port Fusio...

Page 60: ...f for 1s The door lock fails to pair with the host The indicator blinks at 4 Hz on for 0 125s and then off for 0 125s Off The power supply is abnormal Press SW Blinki ng interm ittentl y at super short interv als The indicator blinks at super short intervals for 0 5s and then off for 0 5s The indicator blinks at super short intervals blinking at 10 Hz on for 0 05s and then off for 0 05s The cycle ...

Page 61: ...20 PAD Table 3 37 Pad structural specifications Item Specifications Dimensions L x W x H 243 mm x 164 mm x 7 8 mm Weight About 460 g Table 3 38 Pad technical specifications Item Specifications Touchscreen 10 1 inch 1920 x 1200 resolution IPS screen and multi touch Storage Machine 32 GB Memory 3 GB LPDDR3 extension card Micro SD a maximum of 256 GB non standard configuration FusionModule500 Smart M...

Page 62: ...oom Photo resolution rear camera up to 8 M 3264 x 2448 pixels front camera up to 1 9 M 1600x1200 pixels Battery Materials Li polymer Capacity 5100 mAh typical value or 4980 mAh rated value WiFi connection web page browse time about 6 5 hours Power adapter charge time about 3 5 hours 5 V 2 A adapter 3 4 3 6 Optional WiFi Module The WiFi module provides WiFi signals for equipment such as pads and mo...

Page 63: ...ndensing Storage humidity 5 90 RH non condensing Power 0 8 W 3 4 4 Optional NetEco Intelligent Data Center Management System 3 4 4 1 System Overview With a flexible structure and modular design the NetEco can manage facilities of one data center or centrally manage facilities of multiple data centers in different regions The management system provides a GUI to implement comprehensive management fu...

Page 64: ...e of the following servers according to the management capability requirement Table 3 40 Server Model Configuration TaiShan 200 Model 2280 standard configuration 2 x Kunpeng 920 48 core 2 6 GHz 4 x 32 GB memory 2 x 1 2 TB 8 x 1 8 TB drives TaiShan 200 Model 2180 basic configuration 1 x Kunpeng 920 32 core 2 6 GHz 2 x 32 GB memory 2 x 1 2 TB drives 2288X V5 H22X standard configuration 2 x 5218 16 c...

Page 65: ...distribution system The cross sectional areas of ground cables are determined according to IEC 60364 5 54 Cabinet Grounding Metal components and parts of cabinets are properly connected A structural connection area is protected and applied with antioxidants An area protected with painting should ensure proper metal surface contact for two connected components The DC resistance is within 0 1 ohm be...

Page 66: ... to route cables from the front to the rear Cable Tray A cable tray is used for forward and backward cabling It uses mounting ears to facilitate device installation Figure 3 23 Cable tray Table 3 42 Cable tray technical specifications Dimensions H x W x D Weight Space Occupied 43 6 mm x 482 6 mm x 250 mm 1 89 kg 1 U FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Issue 02 ...

Page 67: ...Specifications and Appearance Protective gloves Marker Measuring tape 5 m Level Step ladder 2 m Phillips screwdriver M4 M6 and M8 Flat head screwdriver 2 5 mm Torque wrench Adjustable wrench 6 Socket wrench M6 M8 and M12 Hex key 5 mm Laser locator FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 57 ...

Page 68: ... tool Polyvinyl chloride PVC insulation tape Wire stripper Hydraulic pliers Wire clippers Crimping tool Multimeter Electroprobe Heat shrink tubing Cable ties Hammer drill Electric screwdriver Rubber mallet FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 58 ...

Page 69: ...ze gloves Cutter Welding torch 5 silver solder Oxygen Acetylene Hot melt device Clamp meter Pipe bender Insulation gloves Pressure gauge 1 PCS a Leather hose 3 PCS a Nitrogenb Reducing valvec Vacuum pumpd Water pipe thread sealante FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 59 ...

Page 70: ...ad sealant with PTEF as the padding Maximum gap 0 5 mm Pressure resistance above 1 6 MPa Compliant with the industry standard JB T7311 2008 Technical Specification for the Application of Anaerobic Glue in Engineering Machinery 4 1 2 Installation Environment Check Ensure that the installation environment meets the requirements before installation Table 4 3 Installation environment checklist Check I...

Page 71: ...NOTE If any of the requirements is not met contact Huawei technical support 4 1 3 Site Equipment Preparation All cabinets and devices have been delivered to the site and checked against the delivery list Cabinets and devices need to be transported to the specified positions based on the detailed equipment room layout diagram and unpacked for further installation CAUTION Pay attention to the follow...

Page 72: ... Cable Connection 1 ECC800 Pro Not required Not required 2 UPS Not required Required 3 Lithium battery Required Required 4 Optional Camera Required Required 5 T H sensor Required Required 6 Water sensor Required Required 7 PDU2000 Not required Required FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 62 ...

Page 73: ...umber of installation personnel varies based on the project progress and installation environment Typically two to three persons are required 4 2 Hardware Installation The angle of door opening by the gas spring is 110 Ensure that the door opening angle is less than 110 4 2 1 Cabinet Transportation and Unpacking Context Only trained personnel are allowed to move the cabinet Remove the packed cabin...

Page 74: ...emove pallets from ordinary cabinets 1 Remove the plastic bag and take out the fitting box 2 Check the cabinet exterior for damage If any damage is found notify the carrier immediately 3 Check against the packing list that the equipment and fittings are correct and complete If some fittings are missing or do not comply with the packing list record the information and contact your local Huawei offi...

Page 75: ... Aisle Containment Prerequisites The cabinets have been transported to the destination place and unpacked Context If the site elevator is too small to transport a cabinet remove the aisle containment from the cabinet Reassemble them after transporting them to the installation position Then perform subsequent operations FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 0...

Page 76: ...he front and rear doors of the cabinet Step 2 Optional Cut off the cable tie on the PAD cable in the cabinet and pull the cable into the cabinet through the front door NOTICE Record the PAD cable route because you need to bind the PAD cable along the original route in subsequent installation Figure 4 3 Removing the PAD cable FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide I...

Page 77: ...he cabinet doors off the hinges Remove the front and rear doors NOTICE The cabinet front door is heavy Arrange at least two persons to carry the door Before removing a cabinet door disconnect the ground cable between the cabinet door and the cabinet FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 67 ...

Page 78: ...igure 4 6 Removing the top plate Step 7 Remove the screws securing the aisle containment to the cabinet using a Phillips screwdriver and remove the aisle containment from the cabinet FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 68 ...

Page 79: ...ferring to Step 7 to Step 2 End 4 2 3 Installing a Cabinet Prerequisites The floor levelness meets engineering requirements Context To position a cabinet perform the following steps 1 Determine the position of the cabinet based on the engineering layout diagram 2 Place the cabinet at the correct installation position FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 ...

Page 80: ... and last rows use a flat head screwdriver to level the anchor bolts in the middle row until they are in close contact with the ground Do not remove the anchor bolts Otherwise rework is required if the cabinet height does not meet requirements Anchor bolt adjustment method Wrench an anchor bolt clockwise to elevate a cabinet leg or wrench an anchor bolt anticlockwise to lower it The anchor bolts c...

Page 81: ...thentic in the following ways 1 Refrigerant from name brands such as DuPont Daikin and Honeywell is recommended 2 Dial the refrigerant vendor s hotline to confirm the refrigerant authenticity 3 Place the refrigerant tank indoors for 24 hours Use a point thermometer to measure the outer surface temperature of the refrigerant tank and connect a pressure gauge to the tank to measure the internal pres...

Page 82: ...on Temperatu re C Gauge Pressure MPa Saturation Temperatu re C Gauge Pressure MPa Saturation Temperatu re C Gauge Pressure MPa 0 0 7 19 1 31 38 2 21 1 0 73 20 1 35 39 2 27 2 0 75 21 1 39 40 2 33 3 0 78 22 1 4 41 2 39 4 0 81 23 1 47 42 2 45 5 0 84 24 1 51 43 2 51 6 0 87 25 1 56 44 2 57 7 0 9 26 1 60 45 2 63 8 0 93 27 1 65 46 2 7 9 0 96 28 1 69 47 2 76 10 0 99 29 1 74 48 2 83 11 1 02 30 1 79 49 2 9 ...

Page 83: ...n oil trap every 6 m to 7 5 m on the gas pipe to ensure that the compressor oil flowing from the vertical gas pipe to the oil trap can be quickly taken away when the compressor restarts after shutdown Figure 4 10 Oil trap unit mm Optional Gas Pipe Liquid Pipe and Thermal Insulation Foam Table 4 6 Specifications Item Specifications Gas pipe 3 8 inch 9 52 mm pressure withstanding capacity 4 5 MPa Fu...

Page 84: ...4 11 shows supports for a refrigerant or water pipe Select supports based on site conditions Figure 4 11 Pipe supports unit mm NOTE The height of a U shaped pipe clamp equals the pipe diameter with thermal insulation foam minus 5 mm The pipe supports are to be purchased by the customer The recommended material for pipe supports and clamps is 304 stainless steel Install a support every 2500 mm in t...

Page 85: ...es are as follows If the outdoor unit is placed higher than the indoor unit the maximum height deviation between them should be less than or equal to 20 m Install an oil trap every 6 m to 7 5 m along the gas pipe in the vertical direction to ensure system reliability If the indoor unit is placed higher than the outdoor unit the maximum height deviation between them should be less than or equal to ...

Page 86: ...edure Step 1 Remove the filler panels from the 1st U to the 5th U of the cabinet Step 2 Push the indoor unit of the smart cooling product into the bottom of the cabinet along the guide rails and secure the indoor unit using M6 screws based on the positions of floating nuts on the cabinet mounting bars FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyr...

Page 87: ...ndicator which can be seen only after the rear panel is opened End 4 2 4 4 Exhausting Nitrogen from an Indoor Unit Context NOTE 0 5 MPa nitrogen is injected into the indoor unit for transportation Nitrogen needs to be exhausted from the indoor unit through the gas pipe needle valve of the indoor unit stop valve Figure 4 15 shows a stop valve FusionModule500 Smart Mini Data Center User Manual 4 Ins...

Page 88: ...t connect a rubber hose and a pressure gauge to the gas pipe needle valve and slowly exhaust nitrogen as shown in Figure 4 17 CAUTION When you connect the rubber hose the pressure gauge valve should be closed When exhausting nitrogen ensure that the rubber hose is secured Otherwise personal injury will be caused as a result of the airflow impact FusionModule500 Smart Mini Data Center User Manual 4...

Page 89: ...an outdoor unit in a damp environment such as a moist basement or rain because the humidity will cause short circuits Environmental Requirements To avoid a fire disaster install an outdoor unit in a dry and well ventilated place without flammable gas leakage Select a place away from direct sunlight and radiation from other heat sources If the sunlight or heat radiation cannot be avoided cover the ...

Page 90: ...he space requirements The baffle plate height and width should be greater than or equal to the outdoor unit height and width respectively If the site installation environment is complicated and the preceding conditions are not met contact Huawei technical support Space Requirements Figure 4 18 Space requirements 4 2 4 5 2 Securing an Outdoor Unit Prerequisites The M10 expansion bolts used for secu...

Page 91: ...mensions and drill holes in the concrete base Step 2 Align the outdoor unit mounting holes with the holes in the concrete base and secure the outdoor unit to the concrete base using four M10 expansion bolts as shown in Figure 4 19 Figure 4 19 Installing an outdoor unit unit mm End 4 2 4 6 Installing a Low Temperature Component Prerequisites When the outdoor temperature is lower than 20 C a low tem...

Page 92: ... with it The low temperature component pipes need to be welded The procedure is as follows 1 Remove the side panel with knock out holes 2 Knock off the sheet metal from the knock out holes on the side panel and fit the side panel into the copper pipes to be welded 3 Weld the liquid inlet pipe and liquid outlet pipe 4 Secure the side panel to the low temperature component FusionModule500 Smart Mini...

Page 93: ...ch as oxide scale in a copper pipe use nitrogen or compressed dry air to clean the copper pipe During maintenance if there are many oil stains in a copper pipe charge a proper amount of trichloroethylene or carbon tetrachloride After the oil stains dissolve blow air to clean the copper pipe Ensure proper indoor ventilation to prevent the operator from being poisoned 2 Clean the air cooled condense...

Page 94: ...and outdoor units Table 4 9 Equivalent length of the straight pipe unit mm Equivalent Length of Components Copper Pipe Diameter Equivalent Length 45 degree Bend 90 degree Bend 180 degree Bend 15 88 150 250 500 12 7 140 250 500 9 52 100 200 340 6 60 120 240 If the pipe between the indoor unit and outdoor unit is longer than 10 m increase the pipe diameter to reduce system resistance The following t...

Page 95: ...all Drill round or rectangular holes at the bottom of the wall for routing connecting pipes drainpipes and power cables When a system pipe passes through the wall the end of the pipe must be effectively sealed to prevent sundries from entering the copper pipe Step 3 Connect pipes Connect copper pipes based on the unit specifications Install the refrigerant pipe and check whether the pipe thread is...

Page 96: ...ant pipe is straight add a support every 2500 mm Figure 4 24 Securing supports NOTE Onsite personnel are responsible for preparing the required materials and installing the supports Step 4 Connect the threaded connector FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 86 ...

Page 97: ...Figure 4 25 Top piping scenario Figure 4 26 Bottom piping scenario FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 87 ...

Page 98: ...een the top of the low temperature component and the bottom of the indoor unit cannot exceed 500 mm Figure 4 27 Pipe connection with a low temperature component top piping Figure 4 28 Pipe connection with a low temperature component bottom piping End 4 2 4 8 Injecting Nitrogen to Preserve Pressure Context NOTICE The measuring range of the pressure gauge must be at least 4 0 MPa and the rubber hose...

Page 99: ... damaged Figure 4 29 Leakage test with nitrogen 1 Nitrogen cylinder 2 Reducing valve 3 Low pressure gauge 4 High pressure gauge 5 Gas pipe needle valve 6 Liquid pipe needle valve Step 3 Inject 3 5 MPa nitrogen and preserve the pressure for 24 hours The system pressure should stay constant under unchanging ambient temperature conditions If there is a considerable temperature change and the pressure...

Page 100: ...tightness test is performed exhaust nitrogen WARNING Do not use compressed air because water and impurities in the air affect the system operation Do not use oxygen or acetylene for a leakage test 4 2 4 9 Connecting Water Pipes Context The water pipes to be connected onsite is the condensate drainpipe which can be routed from the top or bottom as required Figure 4 30 Holes in the smart cooling pro...

Page 101: ...rainpipe inside the indoor unit must be wrapped with the thermal insulation tubing in fittings Figure 4 31 Drainpipe routed from the top End Bottom Piping Step 1 Take out a drainpipe connector from the fitting bag and put the connector on the other end of the drainpipe as shown in Figure 4 32 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huaw...

Page 102: ...e requirements The drainpipe inside the indoor unit must be wrapped with the thermal insulation tubing in fittings 1 Remove the baffle plate from the water pipe hole at the bottom of the cabinet Figure 4 33 Removing the baffle plate from the bottom of the cabinet FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 92 ...

Page 103: ...the water pan until the low float switch is raised and check whether drainage is normal Step 2 Ensure that the condensate pipe is not bent during installation and connection End 4 2 4 10 Connecting Cables The indoor unit uses the single phase power supply from the smart cooling product control unit The outdoor unit is energized by the power distribution unit in the cabinet FusionModule500 Smart Mi...

Page 104: ...ork control CAN port 6 T H sensor port Figure 4 36 shows the cable connections to the smart cooling product Figure 4 37 shows the cable route between the electrical port on the indoor unit and the outdoor unit FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 94 ...

Page 105: ...ctions to the smart cooling product Figure 4 37 Cable route between indoor and outdoor units FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 95 ...

Page 106: ...he unit are set before delivery Do not adjust them by yourself Cables must be routed through protective tubes for protection Power Supply to the Low Ambient Kit Power supply mode Connect the outdoor unit terminals to the low ambient kit Connect the brown cable to the L phase of 220 V AC and the blue cable to the N phase of 220 V AC NOTICE The brown cable and blue cable are two core low temperature...

Page 107: ...e and liquid pipe of the outdoor unit are closed NOTICE Vacuumization is required for the indoor unit outdoor unit and low temperature component During vacuumization open the stop valve of the indoor unit and exhaust air from the gas pipe needle valve and liquid pipe needle valve of the indoor unit Do not exhaust air from only one end If a unit is configured with a low ambient kit exhaust air from...

Page 108: ... open the pressure gauge alternatively for several times The position of the pressure gauge pointer and the noises made by the vacuum pump do not change Otherwise the cooling system may not be sealed properly Step 5 Check that the time for vacuumization is 80 minutes or longer after ensuring that the cooling system does not leak and that the pressure displayed on the vacuum pump is less than or eq...

Page 109: ...dded to the unit based on the standard pipe length before delivery If the pipe between the indoor unit and outdoor unit is longer than 10 m add refrigerant oil to the system to ensure normal system operation The following lists the amount of refrigerant oil to be added for each 1 m increase in the length of the pipe connecting the indoor and outdoor units Formula for calculating the amount of refr...

Page 110: ...rack mounted smart cooling product without a low ambient kit plus 2 kg If the pipe between the indoor unit and outdoor unit is longer than 10 m add refrigerant to the system to ensure normal system operation The following table lists the amount of refrigerant to be added for each 1 m increase in the length of the pipe connecting the indoor and outdoor units Table 4 11 Amount of refrigerant to be a...

Page 111: ...rances should be reserved The space for each lithium battery should be at least 3 U The lithium batteries cannot be directly stacked or vertically placed Install lithium batteries from bottom to top Step 2 Install the protective covers for the positive and negative poles of the lithium batteries Step 3 Install other lithium batteries in the same way End 4 2 5 2 Optional Installing Busbars Prerequi...

Page 112: ... the lithium battery configuration Figure 4 42 Installing busbars End 4 2 5 3 Installing PDU2000s Context Two half height rPDUs for vertical installation are configured Procedure Step 1 Install a half height PDU2000 1 Open the cabinet rear door 2 Secure the half height PDU2000 to the installation position using screws Step 2 Install the other PDU2000 in the same way FusionModule500 Smart Mini Data...

Page 113: ...d the positions of the signal cables connected to the panel of the ECC800 Pro main control module and then disconnect the signal cables Step 2 Remove the ECC800 Pro main control module and then insert the SIM card into the left slot of the ECC800 Pro main control module NOTE The SIM card needs to support LTE WCDMA or GSM FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue...

Page 114: ...the recorded position Step 4 Install the antenna 1 Attach the antenna to the middle of the cabinet top 2 Route the antenna cable into the cabinet through the signal cable hole at the top of the cabinet and then to the appropriate port on the ECC800 Pro FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 104 ...

Page 115: ... the ECC800 Pro Figure 4 47 Installing an antenna cable End 4 2 6 2 Installing a PAD Context The PAD is to be installed on the front door of the cabinet FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 105 ...

Page 116: ... position Procedure Step 1 Adjust the width and height of the PAD support to match the dimensions of the PAD to be installed FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 106 ...

Page 117: ... secure the support to the front door Figure 4 50 Removing the nut Step 3 Route the PAD power cable to the cable hole in the PAD support and connect the cable to the PAD Step 4 Adjust the feet above the PAD support and clamp the PAD to the PAD support FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 107 ...

Page 118: ...all a T H sensor 1 Open the front and rear doors of the cabinet 2 Unpack the two T H sensors and attach one to the 33 U position on the right post of the front door and the other to the 3 4 U position on the right post of the rear door of the cabinet NOTE The installation positions of the T H sensors can be adjusted as required Step 2 Set the DIP switch address of the T H sensor on the front door ...

Page 119: ...e front door and the other to the 34th U position on the rear door of the cabinet NOTE The installation positions of the T H sensors can be adjusted as required Step 2 Set the DIP switch address of the T H sensor on the front door to 2 and that of the T H sensor on the rear door to 1 Table 4 13 DIP switch setting on a T H sensor Address DIP Switch Sequence No 1 2 3 4 5 6 1 ON OFF OFF OFF OFF OFF 2...

Page 120: ...cable is required connect the male connector of a water detection cable to the female connector of another One water detector can be connected to a maximum of nine water detection cables Figure 4 52 Water sensor 1 Water detector 2 Conversion cable end A connected to the water detector 3 Conversion cable 4 Conversion cable end B connected to the water detection cable 5 Water detection cable end A c...

Page 121: ...installation position for the fastener of the water detection cable Ensure that the water detection cable placed on the fastener is in good contact with the floor Step 4 Tear off the protection paper from the rear of the fastener and then securely attach the fastener to the floor If the fastener cannot be securely attached to the floor go to Step 5 If the fastener is securely attached to the floor...

Page 122: ... water detection cables are connected in series connect the male connector of one cable to the female connector of another End 4 2 6 6 Installing an Electrode Water Sensor If the water sensor is required perform the following steps to install it Procedure Step 1 Place the water sensor on the floor under the cabinet Step 2 Route the water sensor cable through the cable hole in the lower cover of th...

Page 123: ... installation position of the server and check whether floating nuts are installed If not install them first Figure 4 58 Installing a floating nut Step 2 Install guide rails FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 113 ...

Page 124: ... push it into the cabinet Step 4 When the two mounting ears on the server contact the mounting bars on the rack tighten the captive screws on the mounting ears to secure the server Figure 4 60 Installing a server Step 5 Connect the server power cable 1 Wear an ESD wrist strap or ESD gloves 2 Connect one end of the power cable to the cable port on the AC power module of the server FusionModule500 S...

Page 125: ...m off the excess of the cable ties End 4 2 6 8 Optional Installing a Camera Prerequisites A camera and tools for installing it have been prepared The network cable used for camera communication has been prepared Context The camera and its mounting plate need to be installed on the top of the front door of the end cabinet FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue...

Page 126: ...SD card 1 Remove the transparent cover using a Phillips screwdriver Figure 4 63 Removing the transparent cover 2 Gently insert the SD card into the SD card slot FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 116 ...

Page 127: ... mounting plate and screw the camera to the mounting plate Figure 4 65 Installing a camera base 1 Cable outlet Step 4 Install the mounting plate with the camera at the top of the front door of the end cabinet as shown in Figure 4 66 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 117 ...

Page 128: ...ra is horizontally installed and the surveillance video is displayed horizontally During the installation adjust the surveillance angle to avoid video image rotation after the installation When adjusting the surveillance angle pay attention to the position of the illuminator to prevent the illuminator from being blocked FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue ...

Page 129: ...ing the transparent cover End 4 2 6 9 Optional Installing a LAN Switch Procedure Step 1 Locate the LAN switch installation position in the cabinet and install guide rails and floating nuts Step 2 Install the mounting ears delivered with the LAN switch and secure the LAN switch to the rack rails at the front of the cabinet NOTE This section describes only the installation method The actual product ...

Page 130: ...nd tighten the captive screws on the power module panel Figure 4 70 Installing a power module for a LAN switch End 4 2 6 10 Optional Installing a VCN510 Context By default the VCN510 is delivered without a disk After the VCN510 is delivered to the site install hard disks as required and then install the VCN510 in the cabinet FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide I...

Page 131: ...rew white that are used to connect the subrack bottom to the front panel Remove the subrack cover and front panel as shown in the lower right figure Figure 4 72 Removing screws 3 Remove the chassis cover Hold the chassis cover with one hand and push the chassis cover towards the front panel with the other hand Then remove the chassis cover with both hands FusionModule500 Smart Mini Data Center Use...

Page 132: ...ws in the package and preinstall the two screws in the holes near the cable outlet on the hard disk backplane Tighten the screw threads for three circles ensure that the screws do not fall naturally Figure 4 74 Installing disk screws 5 Insert the SATA and power cables into the corresponding ports on the hard disk During cable connection ensure that the metallic plate of the SATA cable faces upward...

Page 133: ...preinstalled screws with the cucurbit holes on the bottom cover of the chassis Then horizontally place the disk Ensure that the screws are in the holes Figure 4 76 Disk installation positions 1 No 1 disk installation position 2 No 0 disk installation position 7 Push the hard disk in the direction shown in the following figure to enable the two preinstalled screw heads to slide into the cucurbit ho...

Page 134: ...te to that for pushing the disk in No 1 position 10 Install the upper cover of the chassis Place the upper cover of the chassis Fasten the three screws on the bottom cover of the chassis and the six screws on the left and right sides of the chassis to fix the upper cover of the chassis Step 2 Install the floating nuts Determine the mounting holes for the VCN510 in the cabinet based on the cabinet ...

Page 135: ...rew M4 x 6 countersunk screws white Use three screws to configure one mounting ear on the left of the front panel and the same way to configure the other ones on the right side Then use a Phillips screwdriver to fasten the screws to fix the mounting ears Figure 4 80 Installing mounting ears Step 4 Install the device Carry the device to be cabinet Ensure that the mounting ears at both sides of the ...

Page 136: ...tep 1 Install hard disks 1 Use a PH2 screwdriver to remove the two black screws on the rear of the chassis cover and take off the chassis cover Figure 4 82 Removing the chassis cover 2 Remove two black screws on each side of the chassis and the silvery white one on top of the hard disk tray raise the hard disk tray by 45 degrees and take out the upper and then lower layers of hard disk tray Figure...

Page 137: ...acing downwards hold the screw in the red framed part to lower the hard disk tray until it is level and fasten the black screws on the left and right sides and the white screw on the top Figure 4 85 Fastening the screw on the panel and the screws on the hard disk tray 5 Connect data and power cables to hard disks Connect hard disk cable ports P0 P3 to hard disks on the lower layer hard disk tray a...

Page 138: ...o 800 mm for additional purchase if required for IVS1800 installation Do not attach rubber feet on the IVS1800 to save space during cabinet installation 1 Confirm the installation location of guide rails in the cabinet Install cage nuts two at the front and three at the back on each side to secure the guide rails at the proper position in the cabinet as shown in the lower left figure The lower rig...

Page 139: ...ower right figure CAUTION Before installing a guide rail check the F L F R labels on the guide rail to identify whether it is for the left or right and which part is the front or rear F L indicates the front end of the left guide rail and F R indicates the front end of the right guide rail Figure 4 89 Installing a guide rail 3 Install a filler panel for guide rails Fasten the M6 screws to install ...

Page 140: ... nut 5 Install mounting ears Use a PH2 screwdriver to secure the mounting ears to both sides of the front panel of the device with four screws on each side When the device is near the front door of the cabinet fasten screws in hole groups 1 and 2 when the device is near the rear door fasten screws in hole groups 2 and 3 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue ...

Page 141: ...abinet 7 Thread M6 screws prepared by the customer through two slotted holes on each mounting ear Fasten the M6 screws using a Phillips screwdriver to fix the mounting ears on the front mounting bars of the cabinet as shown in the lower right figure Figure 4 93 Securing the device Step 3 Power on the device 1 Turn on the power switch 2 Check the indicators on the front panel of the device for its ...

Page 142: ...ed in some positions that may affect cable installation If a label conflicts with a cable tie attach the label to the outer side of the cable tie Attach labels to both ends of a cable Requirements for Neatly Routing and Binding Cables To route and bind cables in an appealing way follow these rules 1 Neatly organize exterior cables in a large bundle of cables and prevent cable tangles that are avoi...

Page 143: ... and DC power cables from diverse non shielded signal cables Keep the cable spacing greater than 100 mm or use grounded metal for isolation purposes Do not bind the cables together Preferentially route the cables along different sides of cabinets 2 You are advised to route network cables and optical cables separately Safety and Reliability Requirements for Routing and Binding Cables 1 Unless other...

Page 144: ...es such as radiators and heat vents If unavoidable take heat resistant measures 7 Keep cables far away from operating components such as fan blades and do not bind cables to an airflow path of fans 8 Prevent rotating components such as doors from squeezing or pulling cables Cable Binding Requirements Bind cables reliably along the route and ensure that the binding interval meets the requirements i...

Page 145: ...cores may break due to strong stress as shown in Figure 4 100 Figure 4 100 Binding cables in a bending area 4 Ensure that the cable ties are wrapped and secured in the same direction and do not generate interference with subsequent operations as shown in Figure 4 101 Figure 4 101 Direction for securing cable ties FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020...

Page 146: ...nd bar in the cabinet to the floor ground bar or collective ground bar Figure 4 102 General ground bar 4 3 3 Cable Connections to the Power Supply and Distribution System 4 3 3 1 Top Cable Routing FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 136 ...

Page 147: ...talled at the cable outlets of the cabinet for ease of cable routing Cut a cross in the middle of a wire bushing using an electrician s knife as shown in Figure 4 104 Figure 4 104 Cutting a cross in a wire bushing Cables can be bound to the side panels and mounting bars of the cabinet FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Techn...

Page 148: ...ion subrack position in the cable connection description is for reference only The actual position prevails Procedure Step 1 Optional Connect input power cables to the PDU 1 Optional Remove the transparent protective panel at the rear of the PDU 2 Connect input power cables to the PDU FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Techn...

Page 149: ... positions on the power distribution subrack irrespective of whether cables are routed through the top or bottom of the cabinet but the cable routes inside the cabinet are different FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 139 ...

Page 150: ...or the signal cable and water sensor cable 3 Hole for the input power cable and battery cabinet power cable 4 Smart Cooling Product refrigerant liquid pipe hole 5 Smart Cooling Product refrigerant gas pipe hole FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 140 ...

Page 151: ...rewdriver diagonal pliers protective gloves Material cable tie Procedure Step 1 Connect the PDU2000 cables NOTICE If PDU2000 cables have been connected onsite go to Step 2 Connect cables to the PDU2000 based on the type of the PDU2000 and the silk screen on the wiring port The following cable connection is for reference only FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide I...

Page 152: ...ect the cord end terminals of the power cables to the PDU2000 wiring ports as shown in Figure 4 110 Figure 4 110 Connecting the PDU2000 power cable End FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 142 ...

Page 153: ...more than one battery is configured onsite connect battery cables The actual number of batteries depends on the onsite configuration Procedure Step 1 Connect power cables between lithium batteries and the UPS 1 Connect the positive battery terminal to the RTN port on the busbar and the negative battery terminal to the 48 V port on the busbar Figure 4 111 Connecting cables between lithium batteries...

Page 154: ...PS 1 After lithium batteries are connected in parallel connect a signal cable to the BMS port of the UPS 2 A build out resistor needs to be installed at the COM OUT port of the lithium battery at the end FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 144 ...

Page 155: ...out NOTE Connect one end of a network cable to the RS485_IN port on the electronic clasp lock on the front door of the cabinet and connect the other end to the COM3 port on the ECC800 Pro Connect one end of another network cable to the OUT port on the electronic clasp lock on the front door of the cabinet and connect the other end of the network cable to the RS485_IN port on the electronic clasp l...

Page 156: ...isites The required cables have been prepared Procedure Step 1 Connect the OUT port on the T H sensor on the front door to the RS485_IN port on the T H sensor on the rear door in series FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 146 ...

Page 157: ...ound terminal on the device and the other end to the ground point on the cabinet A Phillips screwdriver and M4 screws are required The ground cable is a yellow and green cable of 16 18 AWG NOTE The customer needs to prepare the ground cable FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 147 ...

Page 158: ...el to start the device End 4 3 4 4 Connecting IVS1800 Cables Prerequisites Cables have been prepared Procedure Step 1 Connect one end of the ground cable to the ground terminal on the device and the other end to the ground point on the cabinet A Phillips screwdriver and M4 screws are required NOTE The customer needs to prepare the ground cable Step 2 Connect one end of the network cable to any GE ...

Page 159: ...g a Cable to the WLDS900 Water Sensor Prerequisites Water sensor cables have been routed The monitoring cables to be connected have been prepared Procedure Step 1 Connect one end of the network cable that has been routed to the water detector to the AIDI_2 port on the ECC800 Pro Figure 4 118 Routing a signal cable End FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02...

Page 160: ...sion Passed Failed 6 The cabinet door and lock work properly Passed Failed 7 All labels are correct clear and complete Passed Failed 8 The cabinet has no waste tape cable ties paper or packing materials around it Passed Failed 9 All components are properly installed and no component is left onsite Passed Failed 10 Block empty cable holes using plugs or lids Passed Failed Cable Installation Check T...

Page 161: ... no short circuit occurs Passed Failed 2 The ground cable AC power cables and internal cables are correctly connected and screws are secured No short circuit occurs during power input or output Passed Failed 3 The smart cooling product input voltage is within the range of rated voltage 10 and the input frequency is within the range of rated frequency 3 Hz Passed Failed 4 The length of ground cable...

Page 162: ... leakage Passed Failed 10 Lithium battery cables are connected correctly Passed Failed 11 DIP switches on devices are correctly set Passed Failed Customer Sign Check Data FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 152 ...

Page 163: ...tion module indicator is green the SPD is running properly If the surge protection module indicator is red the surge protection module is faulty and must be replaced immediately Step 2 Switch on the power input circuit breaker outside the cabinet to power on the cabinet Step 3 Switch on the UPS input circuit breaker Step 4 After the UPS starts set parameters such as the battery capacity based on t...

Page 164: ...itial password is 001 Enter the correct password to enter the UPS setting mode Figure 5 1 Standby mode Step 3 Setting the output voltage based on site requirements Output Voltage Description You need to shut down the inverter before changing the output voltage 220 indicates that the output voltage is 220 V AC 230 indicates that the output voltage is 230 V AC default value 240 indicates that the ou...

Page 165: ...e lithium batteries communicate properly If the running indicator on a lithium battery is steady on the lithium battery communicates properly with the SMU If the indicator blinks fast 4 Hz the communication is interrupted In this case check that the communications cable is properly connected Step 3 Observe the lithium batteries for 15 minutes The batteries are running properly if the alarm indicat...

Page 166: ...e gas pipe for the outdoor unit is open Procedure Step 1 Switch on the circuit breakers for the indoor and outdoor units in the upstream PDB NOTICE The electric heating belt of the crankcase starts working Before starting the compressor ensure that the electric heating belt of the crankcase has been preheated for more than 12 hours Otherwise maintenance is not guaranteed Step 2 Commission the syst...

Page 167: ...mounted HR04A is properly connected to the ECC800 Pro If the connection is normal click Confirm The connected devices are displayed in the Number of connected devices list If the connection is abnormal check whether the device is properly connected to the ECC800 Pro whether the device and the ECC800 Pro are running properly and whether the parameter settings are consistent with the device paramete...

Page 168: ...the length of the straight pipe between the indoor and outdoor units to obtain the total one way pipe length L L should be less than or equal to 60 m If L exceeds 60 m contact Huawei technical support Table 5 2 Equivalent length of pipe components Pipe Outer Diameter 90 degree Bend 180 degree Bend 3 8 inch 9 52 mm 0 3 m 0 6 m 2 9 inch 6 mm 0 2 m 0 4 m For a 5 U rack mounted smart cooling product w...

Page 169: ... ensuring that no refrigerant is required Users include admin preset password Changeme and operator preset password Changeme To enter the diagnostic mode log in as user admin If a smart cooling product is not configured with a heater or humidifier skip the commissioning steps related to the electric heater and wet film humidifier The heater and humidifier do not work at the same time Procedure Ste...

Page 170: ...alve at the joint of the gas pipe needle valve and then charge refrigerant at the gas pipe needle valve NOTICE Do not move the hose or refrigerant cylinder when charging refrigerant Otherwise the reading on the electronic balance will be affected 7 Charge liquid refrigerant based on the amount provided in Amount of refrigerant to be added 8 After the refrigerant is charged close all pressure gauge...

Page 171: ... correct direction End 5 3 Management System Power On Commissioning 5 3 1 Preparations and WebUI Login Prerequisites Supported operating system Windows 7 and later versions It is recommended that the screen resolution be 1366 x 768 or higher Browser Chrome Firefox Internet Explorer 11 or later Procedure Step 1 Connect a network cable between the PC network port and the WAN1 port protected by a sec...

Page 172: ...If the WAN1 port IP address is 192 168 8 10 subnet mask is 255 255 255 0 and default gateway is 192 168 8 1 set the PC IP address to 192 168 8 12 subnet mask to 255 255 255 0 and default gateway to 192 168 8 1 Step 3 Set LAN parameters NOTE If the ECC800 Pro connects to a LAN and a proxy server has been selected perform Step 3 3 and Step 3 4 If the ECC800 Pro connects to the Internet and the PC in...

Page 173: ...o on your PC you are advised to clear the historical Internet Explorer cache Failing to do so may cause some information missed or exception after login The following provides the details 1 Open Internet Explorer and choose Tools Internet Options General 2 Select Delete browsing history on exit and click Delete 3 In the Delete Browsing History dialog box select all options except Password and clic...

Page 174: ... If you forgot the password you will be unable to log in to the WebUI When the event notification is configured and the password retrieval mode is configured under user management the password can be retrieved An account is logged out due to timeout if no operation is performed within 10 minutes after system login A maximum of three users can log in to the ECC800 Pro WebUI at the same time End 5 3...

Page 175: ... using a PC Choose Maintenance App Obtaining scan QR code and save the app installation package to the PC or a path on the mobile storage device Then copy the app installation package to a mobile phone or pad When the WiFi is enabled enter https 192 168 245 10 in the address bar of the Firefox browser version 41 0 or later on a mobile phone or pad and press Enter to access the ECC800 Pro WebUI Cho...

Page 176: ...d click Submit 4 If this is the first time you enable the WiFi function set WiFi Password and click OK 5 Enter the password currently used for logging in to the WebUI and click Submit 6 Specify WiFi SSID and WiFi Password and click Submit to change the SSID and password NOTE If you have set a password when enabling WiFi for the first time you do not need to set the password again The WiFi function...

Page 177: ...is required only during initial power on commissioning If the authentication has been performed successfully no authentication is required afterward The startup password needs to be authenticated when you restore the default settings on the WebUI or by pressing keys If the startup password authentication is not complete the ECC800 Pro WebUI and app cannot be used for commissioning When the system ...

Page 178: ... the first time to enable WiFi after delivery If you enable WiFi on the WebUI there is no default password After the WiFi function is enabled the password for a mobile phone to connect to the WiFi network is Changeme When you log in to the app using a pad the system prompts you to change the password After you disable the WiFi hotspot function on the WebUI and press the button again the WiFi funct...

Page 179: ...upports only the Android system The iDCService app is available only in Chinese End 5 3 4 How Can I Set the Date and Time Procedure Step 1 Choose System Settings System Parameters Time Step 2 Set the time zone date and time or click Obtain local time Then click Submit Step 3 Optional If you want to use the NTP server for time synchronization select NTP server sync Enter NTP primary server IP Wheth...

Page 180: ...een connected to the RS485 port on the UPS2000G and the other end has been connected to the COM4 port on the ECC800 Pro Procedure Step 1 Add a UPS2000G L 1 Log in to the ECC800 Pro WebUI as an administrator 2 Add a UPS2000G L Table 5 5 Adding a UPS2000G L Path Parameter Setting Choose System Settings Device Management and click Add Device The parameters for adding Device attribute Select UPS from ...

Page 181: ...ro are running properly and whether the parameter settings are consistent with the device parameters End 5 3 8 Commissioning Sensors 5 3 8 1 Setting and Adding a Smoke Detector Connected to an AI DI Port on the ECC800 Pro If a smoke detector is installed perform the following steps to configure it Context If the detector is prefabricated only check its settings Procedure Step 1 Set smoke detector ...

Page 182: ... T H sensor and the other end has been connected to the COM port on the ECC800 Pro Procedure Step 1 Set a device address for the T H sensor Operate the DIP switch on the T H sensor to set the device address for the sensor Toggle switches 1 to 6 specify the device address in binary mode ON indicates 1 and OFF indicates 0 Figure 5 8 DIP switch definitions for T H sensors NOTE Numbers 1 and 2 indicat...

Page 183: ...vice address for the T H sensor based on the actual situation 3 Click Test Connect to check whether the T H sensor connects to the ECC800 Pro properly If the connection is normal click Confirm The connected devices are displayed in the Number of connected devices list If the connection is abnormal check whether the device is properly connected to the ECC800 Pro whether the device and the ECC800 Pr...

Page 184: ...rt on the ECC800 Pro Context To use the AI DI sensor enable the corresponding AI DI port and name the sensor The specific alarm then can be reported If the sensor is prefabricated only check its settings The actual value prevails Only the method of the parameter settings is described Procedure Step 1 Set water sensor parameters NOTE The default alarm severity of the AI DI port is Minor If you want...

Page 185: ...he AI DI port on the rack environment unit Context To use the AI DI sensor enable the corresponding AI DI port and name the sensor The specific alarm then can be reported If the sensor is prefabricated only check its settings The actual value prevails Only the method of the parameter settings is described Procedure Step 1 Set water sensor parameters NOTE The following describes how to connect a wa...

Page 186: ...inet door lock is leveled to 2000 3 mm If not adjust it Step 2 Optional If the cabinet door still cannot be opened after step 1 is performed adjust the position of the cabinet electronic clasp lock by using the slotted holes until the cabinet door can be opened and closed properly Step 3 Set device addresses for cabinet electronic clasp locks A cabinet electronic clasp lock is installed at the fro...

Page 187: ...UI as an administrator 2 Create a cabinet view in Smart Module View on the home page 3 Add a cabinet electronic clasp lock Table 5 12 Adding a cabinet electronic clasp lock Path Parameter Setting Choose System Settings Device Management and click Add Device Device Attribute Cabinet Electronic Clasp Lock Device Type Cabinet Electronic Clasp Lock Connect To ECC800 Pro Communicat ions Port COM2 Devic...

Page 188: ... the WebUI Change the cabinet electroni c clasp lock name Click the Running Parameters tab Change the cabinet electronic clasp lock name Remotely open a cabinet electroni c clasp lock Click the Controls tab Select Open the door on Controls and click Submit to remotely open the door Open cabinet electroni c clasp locks in batches Choose Monitoring Cabinet and click the Controls tab Select Open fron...

Page 189: ...sition of the lock tongue Figure 5 11 Adjusting the position of a lock tongue 3 Check whether there is interference between the castors and the door sill at the bottom of the cabinet If so remove the fasteners that secure the castors FusionModule500 Smart Mini Data Center User Manual 5 Power On Commissioning Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 179 ...

Page 190: ...h a 4G module and supports 2G 3G 4G SIM card access NOTE 1 The ECC800 Pro supports only SMS notification service but not data service by using the 4G module 2 China 2G and 4G networks support China Unicom or China Mobile SIM cards and 3G networks support only China Unicom SIM cards 3 Outside China Select SIM cards according to the following wireless modes and frequency bands 4G wireless mode FDD L...

Page 191: ... network operator 2 Click Test to check the email sending If an email fails to be sent check the outbox settings and DNS Server Address If the email is sent successfully click Submit NOTICE If Test email sending failed is displayed check whether the receiver s email server requires CA certificate verification If it is required download the CA certificate from the receiver s email website and uploa...

Page 192: ...d QQ Mail If the email type is not in the list set parameters by referring to the help information of the email type 163 Mail smtp 163 com Non encryption 25 SSL encryption 465 126 Mail smtp 126 com Non encryption 25 SSL encryption 465 QQ Mail smtp QQ co m SSL encryption 465 Sohu Mail smtp sohu c om Non encryption 25 139 Mail smtp 139 com Non encryption 25 Hotmail smtp mail outloo k com TLS encrypt...

Page 193: ...ox parameters for receiving emails are correctly set Step 4 Add a mobile number to receive event notifications NOTE The mobile phone number is used only for configuring the SMS function and is not used for other purposes The phone number is encrypted during transmission in the ECC800 Pro to ensure that the personal data of users is fully protected FusionModule500 Smart Mini Data Center User Manual...

Page 194: ...navailable Failed to send the test short message is displayed Check whether the mobile phone number is correctly set Step 5 Set the alarm notification delay parameter and the new alarm notification parameter Figure 5 16 Setting the alarm notification parameters FusionModule500 Smart Mini Data Center User Manual 5 Power On Commissioning Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 184 ...

Page 195: ...mail parameter settings click Modify or Delete 5 3 11 Video Management 5 3 11 1 Preparing Documentation Before commissioning a camera prepare the following documents in addition to this document Table 5 15 Documentation for commissioning preparation Component Document C3220 Huawei C Series SDC 8 0 1 Product Documentation VCN510 VCN510 VCN520 VCN540 Product Documentation IVS1800 IVS1800 8 1 0 Produ...

Page 196: ...e PC IP address and the camera IP address in the same network segment Enter the camera IP address 192 168 0 120 by default in the address bar of the Internet Explorer and press Enter NOTE The following lists the requirements for the operating system and browser of the camera WebUI Supports Windows 7 Internet Explorer 10 11 Chrome 38 FireFox 35 51 Supports Windows 8 Internet Explorer 10 11 Chrome 3...

Page 197: ...ternet 4 Click Custom level The Security Settings Internet Zone dialog box is displayed 5 Set Automatic prompting for ActiveX controls to Enable and set Download unsigned ActiveX controls and Initialize and script ActiveX controls not marked as safe for scripting to Prompt 6 Click OK Enable TLS 1 1 or TLS 1 2 NOTE You must enable TLS 1 1 or TLS 1 2 when the HTTPS protocol is used to access the cam...

Page 198: ...isable 6 Click OK Step 2 Commission cameras and set parameters for them For details see the delivered documents 1 Preview the site situation in real time and check the camera coverage through videos Adjust the lens if necessary 2 On the View tab page click the Network Time tab to access the Network Time tab page Figure 5 19 Setting the IP address FusionModule500 Smart Mini Data Center User Manual ...

Page 199: ...g with a value that ranges from 1 to 223 IPv4 gateway Gateway IP address of the network where the camera is located The default value is 192 168 0 1 IPv4 subnet mask Subnet mask of the network where the camera is located The default value is 255 255 255 0 Primary DNS Primary DNS IP address The default value is 0 0 0 0 Secondary DNS Secondary DNS IP address The default value is 0 0 0 0 3 On the Vie...

Page 200: ...camera can automatically adapt to scenarios to reduce the bit rate and save the storage space A higher intelligent encoding level indicates more significant reduction of the bit rate which however may lead to image quality deterioration Slice This parameter is available only when you set Encoding protocol to H 264 Multi slice encoding indicates that video streams are divided into multiple segments...

Page 201: ...es clearer images and higher bandwidth consumption Bit rate type This parameter is available only when you set Encoding protocol to H 264 or H 265 The bit rate is measured by data bits transmitted in a unit of time Variable bit rate The bit rate varies depending on the image complexity to ensure the clarity of images with great dynamic changes The bit rate is low if the image is simple or static T...

Page 202: ...n you set Encoding protocol to H 264 or H 265 An I frame is an intra coded frame that represents a fixed image independent of other picture types Each group of pictures GOP begins with this type of frame A smaller I frame interval indicates better video quality and higher bandwidth consumption Layered encoding This parameter is available only when you set Encoding protocol to H 264 or H 265 To ena...

Page 203: ... referring to the Preparing Documentation section 1 Preview the site situation in real time and check the camera coverage through videos Adjust the lens if necessary 2 Set IPv4 address IPv4 subnet mask and IPv4 gateway address to the planned values Figure 5 22 Setting the IP address of the camera 3 Format the SD card a Choose Settings System Configuration Storage Management b The Storage Managemen...

Page 204: ...ol Resolutio n Frame Rate I Frame Interval Minimum Bit Rate Required Supporte d Video Storage Duration h H 265 1080P 25 50 1 Mbit s 66 H 264 1080P 25 50 1 Mbit s 66 H 265 720P 25 50 0 8 Mbit s 75 H 264 720P 25 50 1 Mbit s 66 H 265 720P 25 50 0 6 Mbit s 105 H 264 720P 25 50 0 8 Mbit s 75 FusionModule500 Smart Mini Data Center User Manual 5 Power On Commissioning Issue 02 2020 12 25 Copyright Huawei...

Page 205: ...ites The default IP address of the VCN is configured before delivery You need to configure the IP address of the PC in the same network segment as the IP address of the VCN The version number is subject to the Quick Start delivered with the VCN Procedure Step 1 Enter the OMU portal address the default address for VCN500 is https 192 168 1 100 8443 the default address for VCN510 VCN520 VCN540 is ht...

Page 206: ...he VCN510 16P is admin Figure 5 26 VCN510 8 rear view Figure 5 27 VCN510 16P rear view If the device is not VCN510 and the software version is V100R003 or later the default user name is admin If the software version is V100R002 or earlier the default user name is Admin End 5 3 11 4 2 Initializing Hard Disks Context When the VCN510 is delivered to the site recording data can be stored only after yo...

Page 207: ... of disks that work independently NON RAID If disks work independently recording data is stored into two disks in sequence ensuring high disk usage However the data storage reliability of disks that work independently is lower than that of RAID 1 Step 5 Click Start A risk warning is displayed Step 6 Click OK The system starts to initialize the disks NOTE The server will be restarted during the ini...

Page 208: ...one disk is synchronizing data in the system partition to the system partition of another disk The synchronization process takes about 20 hours which does not impact services During this process do not remove and insert disks If the OMU portal stays at the Local Disk tab page even if users do not perform any operation for a long period of time the OMU portal will not automatically return to the lo...

Page 209: ...ding to the site requirements Figure 5 32 Configuring the server NOTE Set Business IP to XXX XXX XXX XXX Subnet mask to 255 255 255 0 and Gateway IP to XXX XXX XXX XXX The values here are examples The actual value prevails The VCN automatically restarts after the IP address is modified The restart takes about 5 minutes After the restart use the new IP address to access the VCN 3 Modify the IP addr...

Page 210: ...rPort delete the parameter value 0 from Value leave the value empty and click Save Figure 5 33 Setting the NAT port number for the MU 7 In the search result click Edit in the row where the value of Parameter Name is NatIP and set Value to the external IP address of the VCN Click Save Figure 5 34 Setting the external IP address of the MU NOTE Set NatIP to the external IP address of the VCN which is...

Page 211: ...ring camera NTP synchronization 4 In the search results click Edit in the row where Parameter Name is NTPIPC and set Value to 1 5 Click Save After the camera NTP synchronization function is enabled the camera after being connected to the server will automatically synchronize time with the server End Follow up Procedure Optional Set up a VCN stack For details log in to the https e huawei com search...

Page 212: ...e Software Download tab click the version and patch number corresponding to the current version and download the Client Package zip software package Figure 5 37 Client Package search result 2 Right click HW_IVS_Client exe and choose Run as administrator from the shortcut menu Use the default installation mode until the installation is complete 3 Right click the client program and choose Run as adm...

Page 213: ...eed to access NOTE If there are multiple VCNs for multiple smart modules you are advised to evenly distribute the cameras to each VCN 3 Click Search in each camera record enter the user name and password in the text boxes and click Verify If the camera is verified successfully select cameras to add and click Next 4 Preview live video images click the camera in the camera list on the left and adjus...

Page 214: ...TE When creating a user you can select Enable account validity period and set Valid from and Valid to to set the account validity period for the created user Figure 5 38 Creating a user 3 Set Multi point logins to a value greater than 2 4 In the Assign Device View Rights area select the cameras to be browsed and queried by the user Set other parameters based on the documentation delivered with the...

Page 215: ...address box and press Enter In the URL IP address indicates the IP address of the IVS1800 The default IP address is 192 168 3 111 NOTE The OMU portal supports Internet Explorer 10 0 and later versions Step 2 Log in to the OMU portal Set the service system and operating system passwords at the first login 1 Setting the password for the admin user of the service system 2 Setting the password for the...

Page 216: ... address internal IP address of the IVS1800 time zone and time according to the site requirements Figure 5 41 Configuring the server Single Mode by default NOTE Set Business IP to XXX XXX XXX XXX Subnet mask to 255 255 255 0 and Gateway IP to XXX XXX XXX XXX The values here are examples The actual value prevails 2 Change the PC IP address to an address in the network segment of the new IVS1800 IP ...

Page 217: ... to MU and click Search 5 In the search result click Edit in the row where the value of Parameter Name is MUNNatIP and set Value to the external IP address of the IVS1800 Click Save Figure 5 42 Setting the external IP address of the MU NOTE Set MUNNatIP to the external IP address of the IVS1800 which is the same as the external IP address mapped by the IVS1800 on the ECC800 Pro 6 Set Module Name t...

Page 218: ... Figure 5 44 Configuring camera NTP synchronization Step 6 Create a user When connecting to the IVS1800 on the NetEco you need to log in to the VCN as a non admin user 1 Log in to the OMU portal as the admin user 2 Choose User Management Add User NOTE When creating a user you can select Enable account validity period and set Valid from and Valid to to set the account validity period for the create...

Page 219: ...s support huawei com enterprise and search for and choose iClient In the search result click the Software Download tab click the version and patch number corresponding to the current version and download the software package Figure 5 45 iClient software package search result 2 Decompress the software package double click the installation program and complete the installation as prompted 3 Right cl...

Page 220: ...When the IVS1800 is added to the iClient by the admin user the iClient checks whether the login password of the admin user has been set If the password is not set log in to the OMU portal to set the password 6 Click Finish to go to the iClient Step 2 Add a camera For details see the documentation delivered with the device or obtain the documentation by referring to the Reference Documentation sect...

Page 221: ...WSDK The IP address segment indicates the start and end IP addresses of cameras 5 You can use IP Address and Vendor to filter the required cameras in the camera search result and select the required cameras Alternatively you can directly select the required cameras in the camera list Then verify accounts The default password of the HWSDK protocol is HuaWei123 Figure 5 49 Verifying accounts FusionM...

Page 222: ... 3 Click the Server Recording tab The tab page for configuring a server based recording plan is displayed 4 Configure a video recording plan NOTE If you set the recording plan policy to All you do not need to set the recording plan time 5 Click Save End 5 3 12 Linkage Control Prerequisites You have obtained the IP address of the ECC800 Pro as well as the user name and password used for WebUI login...

Page 223: ...ECC800 Pro generates a door open alarm After the smoke alarm is cleared you need to manually close the door After the door is closed the door open alarm is cleared If the emergency heat dissipation control logic conflicts with the smoke alarm control logic the smoke alarm control logic takes precedence NOTE If the fire extinguishing system is installed inside the smart module the linkage function ...

Page 224: ...signal name 1 Choose System Settings Signal Name Modify The Batch Signal Configuration tab page is displayed 2 Set Device type to ECC800 set Device name to ECC800 and click OK 3 On the query result tab page set the new signal name of AI DI_1 to Smoke and click Submit Step 6 Enable the AI DI device 1 Choose Monitoring System ECC800 Running Parameters AI DI_1 Port Settings 2 Set Smoke sensor to Enab...

Page 225: ...trator 2 Choose System Settings Signal Name Modify The Batch Signal Configuration tab page is displayed 3 Set Device type to ECC800 set Device name to ECC800 and click OK 4 On the query result tab page set the new signal name of AI DI_3 to Fire and click Submit Step 6 Enable the AI DI device 1 Choose Monitoring System ECC800 Running Parameters AI DI_3 Port Settings 2 Set Fire sensor to Enable Clic...

Page 226: ... Pro WebUI Table 5 23 IP parameters Path Parameter Default Value Setting System Settings System Parameter s Monitor IP WAN_1 IP address 192 168 8 1 0 Set this parameter based on the IP address assigned by the network administrator Subnet mask 255 255 25 5 0 Set this parameter based on the subnet mask assigned by the network administrator Default gateway 192 168 8 1 Set this parameter based on the ...

Page 227: ...tem Settings NMS Application NetEco Set Authenticati on Password Authenticatio n password Modifyme _123 Set this parameter based on customer requirements NOTE Requirements for setting passwords a z A Z 0 9 _ 8 32 characters that include at least three of the following types lowercase letters uppercase letters digits and special characters Confirm authenticatio n password Step 5 Click Submit End 5 ...

Page 228: ...er Procedure Step 1 Ensure that the power cables and ground cables are securely connected with correct polarity and good contact Step 2 Ensure that the input power supply of the PDB is off Use a multimeter to test the resistance between the power outputs of the PDF and between the working ground and protective ground It is required that short circuit not occur between power outputs or between the ...

Page 229: ...nging If the number of online users reaches the maximum number supported by the system a message is displayed indicating that you cannot log in In this case contact the system administrator After you enter the incorrect password for three consecutive times you must enter the verification code upon the fourth login After you enter the incorrect password for five consecutive times the user account o...

Page 230: ...000 V600R009 Version Mapping from Support Software Network Energy Data Center Facility Fusion Modular Data Center iManager NetEco 6000 Based on the actual NE types and versions to download the mediation software installation package Step 2 Choose System Configuration Adapter Management from the main menu Step 3 Click Upload On the displayed Upload Adapter Package page click and select the files to...

Page 231: ...r ContainerDC You can create Modular Park NetecoSite FusionModule500 and under Subnet You can create DDF Battery Cabinet Rack Modular Power Cabinet and Fire Protection Cabinet and Rack Custom under NetecoSite You can create DDF Battery Cabinet Rack Power Cabinet Fire Protection Cabinet and Rack Custom under Modular You can create DDF Battery Cabinet Rack Modular Power Cabinet Fire Protection Cabin...

Page 232: ...he configuration is complete Step 3 Click on the toolbar End 5 3 13 1 9 Adding a Smart Module This section describes how to create a smart module in the root node subnet equipment room container or site management domain Prerequisites You have logged in to the NetEco client using a web browser You have created management domains in Data Center Planning For detailed operations see Creating a Domain...

Page 233: ...ment Info of the smart module or retain the default values and then click NOTICE The parameters with are mandatory End Follow up Procedure Perform the following operations in the Data Center Planning page as required FusionModule500 Smart Mini Data Center User Manual 5 Power On Commissioning Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 223 ...

Page 234: ...u delete subdevices in the module Delete one smart module 1 Select Modular and click Delete under as shown in Figure 5 54 Figure 5 54 Deleting one smart module 2 In the displayed Confirm dialog box click Yes Delete multiple smart modules in batches 1 Click on the toolbar to display the Figure 5 55 page FusionModule500 Smart Mini Data Center User Manual 5 Power On Commissioning Issue 02 2020 12 25 ...

Page 235: ...u Need To Then Figure 5 55 Deleting multiple smart modules in batches FusionModule500 Smart Mini Data Center User Manual 5 Power On Commissioning Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 225 ...

Page 236: ... added you can set attributes for the component in the Component Info list in the right pane The system automatically displays values for Parent Name and Control Type and you do not need to manually set them you only need to set Name 4 In the upper area of the current page click 5 3 13 1 10 Creating an ECC800 Pro on the NetEco Prerequisites You have logged in to the NetEco client using a web brows...

Page 237: ... Adding an ECC800 Pro device to the smart module NOTE Click OK and you can view the task information including Type Device Name Region Progress Status Start Time End Time and Information in the displayed Progress window 5 3 13 2 CloudOpera NetEco Management 5 3 13 2 1 Logging In to the EDCM Using a Web Client Prerequisites You have obtained a valid user name and password You have created a free tr...

Page 238: ...umber of online users reaches the maximum number supported by the system a message is displayed indicating that you cannot log in In this case contact the system administrator After you enter the incorrect password for three consecutive times you must enter the verification code upon the fourth login After you enter the incorrect password for five consecutive times the user account or the IP addre...

Page 239: ...named Procedure Step 1 Import the obtained digital certificate to the cer directory of the EDCM folder on the mobile client Step 2 On the mobile client tap the icon of the EDCM app The login screen of the app is displayed Step 3 Tap to access the Settings screen Step 4 Tap Replace the certificate to access the Cert Change screen Step 5 Select the new certificate and tap Yes in the displayed dialog...

Page 240: ...or three consecutive times the system automatically displays Verification code Step 3 Tap Log In NOTE If no data is displayed on the screen or a message indicating a network error is displayed check whether the mobile device has properly connected to a WiFi or mobile network If the network is normal check whether you have been forcibly logged out on the NetEco End 5 3 13 2 6 Setting EDCM Communica...

Page 241: ...ngs NMS Application Step 4 Select the NetEco tab In the Communication Parameters area set parameters such as NetEco Deployment Location Server IP and Port Number and click Submit Table 5 26 EDCM parameters Parameter Setting NetEco Location Local Server IP Specifies the IP address of the EDCM server NOTE The IP address of the EDCM server must be on the same network as the IP address of the ECC800 P...

Page 242: ...e of the network ESN ESN of the ECC controller NOTE Tap to scan the QR code on the ECC controller to obtain the ESN Longitude Longitude of the network You can manually enter the value or use GPS to locate Latitude Latitude of the network You can manually enter the value or use GPS to locate Customer Information Customer information FusionModule500 Smart Mini Data Center User Manual 5 Power On Comm...

Page 243: ...Parameter Description Address Address of the network End FusionModule500 Smart Mini Data Center User Manual 5 Power On Commissioning Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 233 ...

Page 244: ...atus of the surge protection module Check the surge protection module indicator and miniature circuit breaker MCB status The surge protection module indicator is steady green The MCB is switched on If the surge protection module indicator is red replace the surge protection module If the MCB is off switch it on FusionModule500 Smart Mini Data Center User Manual 6 O M Issue 02 2020 12 25 Copyright ...

Page 245: ...n Liquid crystal display LCD According to the status icons on the LCD all units are operating properly No fault or alarm information is found in the active and historical alarm records If an alarm is present rectify the fault by checking the device status and parameters Lithium battery Battery management alarm No battery management alarm is generated Identify the cause of an alarm based on the ala...

Page 246: ...ging 20 C to 45 C discharging 2 Battery charge and discharge conditions meet the requirements specified in the battery specifications 1 Identify the cause of an abnormal battery operating temperature 2 If the fault persists contact Huawei technical support ECC800 Pro AC input Input voltage 200 240 V AC Frequency 45 55 Hz If the input voltage is abnormal check the power grid status and input cable ...

Page 247: ...RH non condensing If the temperature or humidity is abnormal check the smart cooling product status Monitoring module indicator The monitoring module indicator is steady green or blinking green If the indicator is off or any abnormal condition occurs see 6 2 2 Management System Troubleshootin g to rectify the fault Network interface indicator The green indicator is steady on and the yellow indicat...

Page 248: ...ntacting Huawei technical support Cable connection The cable connection is secure Secure loose cables Cables are not damaged Replace damaged cables Camera Camera availability On the ECC800 Pro WebUI choose Maintenance Manage Video Video Info to enter the video view page Type the camera name or IP address to find the camera and click View to view the real time monitoring page The monitoring page is...

Page 249: ...rminals and cables Measurement of the ambient temperature of the intelligent battery monitoring system The ambient temperature of the intelligent battery monitoring system is lower than 45 C Locate the cause of an abnormal temperature Water sensor and water detection cable Functions of the water sensor and water detection cable Place the water detection cable into the water and check whether a wat...

Page 250: ...le If the MCB is off switch it on UPS Operating environment Ambient temperature 0 C to 40 C Humidity 0 95 RH non condensing If the temperature or humidity is abnormal check the smart cooling product status If the input voltage is abnormal check the power grid status and input cable connection LCD According to the status icons on the LCD all units are operating properly No fault or alarm informatio...

Page 251: ...of batteries and battery capacity meets requirements Reset the parameters Power cables and terminals between the UPS and the power distribution subrack The insulation layer of cables is intact and terminals are free from noticeable sparks Replace damaged cables Secure output terminals Lithium battery Battery management alarm No battery management alarm is generated Identify the cause of an alarm b...

Page 252: ...temperature 1 Battery operating temperature 0 45 C charging 20 C to 45 C discharging 2 Battery charge and discharge conditions meet the requirements specified in the battery specifications 1 Identify the cause of an abnormal battery operating temperature 2 If the fault persists contact Huawei technical support Battery management parameter settings Check that the settings of battery management para...

Page 253: ...the faulty cable Battery voltage Equalized charging voltage 53 5 V DC Float charging voltage 53 4 V DC 1 Check whether the equalized charging voltage and float charging voltage of a battery are normal 2 If the charging voltage of a battery exceeds the specifications requirement perform a complete forcible equalized charging for the battery and check again whether the voltage is normal 3 If the fau...

Page 254: ...le connection Output voltage Output voltage 53 5 V DC 5 If the output voltage is abnormal check the load power and cable connection Indicator The indicator on the power module is steady green Check the output voltage and determine whether the power module is faulty If the power module is faulty replace it Fan No abnormal noise is generated If abnormal noise is generated clean the fan Operating env...

Page 255: ...stem or WebUI Export smart cooling product logs alarms temperature humidity as well as the operating status and time of the water sensor door status sensor temperature sensor and smoke sensor from the management system View the historical alarms generated in this quarter and select the most common five ones If an alarm is generated handle the alarm by referring to 6 3 Alarm References and 6 2 2 Ma...

Page 256: ...a Camera Intelligent lithium battery monitoring system Battery management alarm No battery management alarm is generated Identify the cause of an alarm based on the alarm information Cleanliness Wipe the battery surface using a piece of white paper and the paper does not turn black Remove dust Battery connection Battery terminals and cables are in good contact Locate poor contact points between ba...

Page 257: ...he surge protection module Check the surge protection module indicator and MCB status The surge protection module indicator is steady green The MCB is switched on If the surge protection module indicator is red replace the surge protection module If the MCB is off switch it on Dust inside the power distribution subrack Check whether there is dust on the power distribution subrack panel The white p...

Page 258: ...ment replace the power cable Insulation performance of the power distribution subrack Measure the insulation resistance using an insulation tester after power off The insulation resistance is greater than or equal to 10 megohms If the insulation performance is poor check and maintain the components in the power distribution subrack such as internal cables and circuit breakers Insulation resistance...

Page 259: ... or alarm information is found in the active and historical alarm records If an alarm is present rectify the fault by checking the device status and parameters Cleanliness Wipe the cabinet surface using a white paper and the paper does not turn black Remove the dust especially from the air filter on the front door or replace the air filter Parameter configuration The configuration of the output vo...

Page 260: ...thout stains 2 The battery terminals are intact 3 Batteries are free from damage and cracks 4 Batteries are free from acid leakage 5 Batteries are not deformed or bulged If the battery appearance is abnormal contact Huawei technical support Battery operating temperature 1 Battery operating temperature 0 45 C charging 20 C to 45 C discharging 2 Battery charge and discharge conditions meet the requi...

Page 261: ... correctly Battery bolts The location of the signs marked on battery terminal bolts indicating tight connections does not change Take photos from multiple angles and contact Huawei technical support Cables between batteries No cable deteriorates and the insulation layer does not crack Replace the faulty cable FusionModule500 Smart Mini Data Center User Manual 6 O M Issue 02 2020 12 25 Copyright Hu...

Page 262: ...t perform a complete forcible equalized charging for the battery and check again whether the voltage is normal 3 If the fault persists contact Huawei technical support Shallow discharge test recommended Conduct a shallow discharge test when the UPS is backed up to verify that the batteries can discharge properly 1 Locate the cause when an exception is identified 2 If the fault persists contact Hua...

Page 263: ...ed off check the reliability of each connection point from positive terminals to negative terminals Check that all points are connected reliably 2 Use a torque wrench to check the tightening torque for each battery screw The torque meets the requirements of the battery manufacturer After checking that the battery screws meet the requirements mark the screws for later check 1 Rectify any abnormal c...

Page 264: ...er the power module is faulty If the power module is faulty replace it Fan No abnormal noise is generated If abnormal noise is generated clean the fan Operating environment Ambient temperature 20 C to 65 C Humidity 0 95 RH non condensing If the temperature or humidity is abnormal check the smart cooling product status Monitoring module indicator The monitoring module indicator is steady green or b...

Page 265: ...and time of the water sensor door status sensor temperature sensor and smoke sensor from the management system View the historical alarms generated in this quarter and select the most common five ones If an alarm is generated handle the alarm by referring to 6 3 Alarm References and 6 2 2 Management System Troubleshootin g or contacting Huawei technical support Cable connection The cable connectio...

Page 266: ...a Camera Intelligent lithium battery monitoring system Battery management alarm No battery management alarm is generated Identify the cause of an alarm based on the alarm information Cleanliness Wipe the battery surface using a piece of white paper and the paper does not turn black Remove dust Battery connection Battery terminals and cables are in good contact Locate poor contact points between ba...

Page 267: ...Rectify the faults based on fault location and fault type NOTICE When a UPS is faulty alarm information is displayed on the LCD Critical alarms must be handled before powering on the UPS again Otherwise the fault may be extended or the UPS may be damaged If the fault is not rectified contact Huawei technical support Table 6 4 Power supply and distribution system troubleshooting Symptom Possible Ca...

Page 268: ... or greater than the upper threshold Use a voltmeter to check whether the UPS input voltage meets requirements The mains is normal but the AC input indicator is off The UPS works in battery mode The UPS mains switch is OFF Turn on the UPS mains switch The input cable is not properly connected Check the UPS input power cable connection The UPS fails to communicate The UPS communications cable is no...

Page 269: ...place batteries Abnormal noise or smell is generated in the UPS cabinet The UPS is faulty Shut down the UPS and cut off the power input immediately Contact your local Huawei technical support The battery indicator blinks The buzzer buzzes 1 second and then stops 1 second The battery reserve is insufficient The UPS is about to shut down The UPS will soon shut down due to insufficient battery reserv...

Page 270: ... whether the AC input is abnormal PSU fault Replace the PSU The Alarm indicator yellow is steady on Overtemperature protection The ambient temperature exceeds the upper threshold Increase the cooling capacity of the smart cooling product The air channel is blocked Unblock it AC input overvoltage or undervoltage protection Check whether the AC input is abnormal The Alarm indicator yellow is blinkin...

Page 271: ...ator green is off There is no AC input If the green indicators on PSUs are steady on the power input to the system is normal Otherwise rectify power grid faults The monitoring module is faulty or not securely installed Reinstall the monitoring module If the fault persists replace the monitoring module 2 RJ45 power output indicators turn off involved ports AIDI_1 AIDI_5 COM1 COM4 and DO The corresp...

Page 272: ... fault Critical The mains has experienced a transient high voltage The output carries special loads such as the inductive and rectification loads The output carries the transformer load but the transformer mode is not enabled The hardware is damaged Rectify the fault and power on the UPS again Check that the load types are supported by the UPS Enable the transformer mode Contact Huawei technical s...

Page 273: ...network cable communication is interrupted Check the cable connection to the smart ETH gateway BCB Tripping Critical The battery has discharged to the end of discharge EOD threshold The battery circuit breaker BCB box is manually disconnected There is a security risk in the battery loop Identify the alarm cause rectify the fault and switch on the BCB box Single Batt terminal off Critical A battery...

Page 274: ... Parts Replacement 6 4 1 Replacing Structural System Components 6 4 1 1 Replacing a Cabinet Electronic Clasp Lock Prerequisites Tool Phillips screwdriver Material A spare cabinet electronic clasp lock is available and functional Context cabinet electronic clasp locks are installed at the front and rear doors of a cabinet Procedure Step 1 Open the front or rear door of the cabinet Step 2 Remove the...

Page 275: ...ctronic clasp lock The mounting holes for the new cabinet electronic clasp lock are slotted holes If the door cannot be properly closed after installation adjust the lock height based on site requirements Step 5 Reconnect the cables to the cabinet electronic clasp lock End 6 4 1 2 Replacing a Gas Spring Prerequisites Tools Phillips screwdriver step ladder Material A spare gas spring is available a...

Page 276: ... spring using an adjustable wrench End 6 4 1 3 Replacing a PDU2000 Prerequisites Tools Phillips screwdriver step ladder Material A spare PDU2000 of the same model is available and functional Context A PDU2000 is installed at the rear door of a cabinet Procedure Step 1 Open the rear door of the cabinet FusionModule500 Smart Mini Data Center User Manual 6 O M Issue 02 2020 12 25 Copyright Huawei Tec...

Page 277: ...s before replacing a power supply and distribution component Power off the upper level equipment before replacing a power supply and distribution component Use a multimeter and electrical tester pen to check whether the front and rear ends of the component to be replaced are powered off after the component is powered off 6 4 2 1 Replacing a Surge Protection Module Prerequisites DANGER Do not repla...

Page 278: ...before replacing the faulty surge protection module Figure 6 4 Measuring voltages Step 4 Hold the faulty surge protection module and pull it out as shown in Figure 6 5 DANGER During replacement do not touch the energized components in the power distribution subrack FusionModule500 Smart Mini Data Center User Manual 6 O M Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 268 ...

Page 279: ... 4 2 2 Replacing a Fuse Prerequisites CAUTION When replacing a fuse wear insulation gloves and do not touch the input copper bar Tool insulation gloves Material The new fuse of the same model is available and functional Procedure Step 1 Shake the fuse terminal block gently pull it out and push it outwards NOTE Fuses can be replaced in a similar way The following figure is for reference only Fusion...

Page 280: ...mart module is securely connected After removing cables wrap exposed terminals with insulation tape and do not block cable labels If cable labels are blocked cables may be connected incorrectly later Step 1 Turn off the battery switch or remove the wiring terminal between the battery and the faulty UPS Step 2 Turn off the corresponding UPS input and output switches Use a multimeter to check whethe...

Page 281: ...requisites Tools insulation gloves Phillips screwdriver socket wrench Material A new battery module is intact The gyroscope function is disabled NOTICE Before the replacement ensure that the load services are not affected or obtain written consent from the customer Procedure Step 1 Switch the BAT battery circuit breaker on the power system to OFF or remove the battery fuse Step 2 Use the Manual ON...

Page 282: ...ing ports Tools ESD wrist strap ESD gloves Phillips screwdriver labels marker Material A spare undamaged and undeformed ECC800 Pro main control module of the same model is available Procedure Step 1 Use the Back Up Current Settings function to record the ECC800 Pro configuration information or manually record the information Path Maintenance Configuration File Back Up Current Settings NOTE If the ...

Page 283: ...k and tighten the screws on both sides of the ECC800 Pro main control module Step 8 Connect the communications cables and antennas to the ECC800 Pro main control module Step 9 Choose Maintenance Configuration File and import the backup configuration file or set parameters for the devices that connect to the ECC800 Pro to ensure normal communication End 6 4 3 2 Replacing an ECC800 Pro PSU Prerequis...

Page 284: ...along guide rails and push the locking latch rightwards to secure the handle Figure 6 9 Replacing a PSU End 6 4 3 3 Replacing an ECC800 Pro Antenna Prerequisites Tools ESD wrist strap ESD gloves Materials A spare ECC800 Pro antenna of the same model is available and functional Procedure Step 1 Remove the 4G antenna Step 2 Install the spare 4G antenna in the original position and connect it to the ...

Page 285: ...in control module and then disconnect the signal cables Step 2 Loosen the screws on both sides of the panel of the ECC800 Pro main control module Step 3 Pull the handles on both sides of the panel of the ECC800 Pro main control module and remove the main control module Figure 6 11 Removing the ECC800 Pro main control module Step 4 Remove the SIM card from the card slot FusionModule500 Smart Mini D...

Page 286: ... the panel of the new ECC800 Pro main control module based on the recorded information End 6 4 3 5 Replacing a Camera Impact on the System The operation of the video surveillance system will be interrupted Preparations Tools ESD wrist strap ESD gloves step ladder label marker Phillips screwdriver Material camera Procedure Step 1 Remove the transparent cover using a Phillips screwdriver FusionModul...

Page 287: ... Remove the SD card Figure 6 15 Removing an SD card Step 3 Remove the monitoring network cable from the camera and remove the camera FusionModule500 Smart Mini Data Center User Manual 6 O M Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 277 ...

Page 288: ...opriate version Step 6 Check that the camera functions properly End 6 4 3 6 Replacing a VCN510 Prerequisites Recommended tool Phillips screwdriver A VCN510 needs to be replaced A spare VCN510 of the same model is available and functional Context NOTICE Videos cannot be recorded during the replacement of the VCN510 FusionModule500 Smart Mini Data Center User Manual 6 O M Issue 02 2020 12 25 Copyrig...

Page 289: ...to be cabinet Ensure that the mounting ears at both sides of the device are tightly attached to the mounting bar in front of the cabinet Use one hand to hold the device Use the other hand to thread M6 screws through the slotted hole on the mounting ear Use a Phillips screwdriver to fix the M6 screws on the mounting ears Each mounting ear uses two M6 screws Figure 6 17 Installing the device Step 4 ...

Page 290: ...fter removing cables wrap exposed terminals with insulation tape and do not block cable labels If cable labels are blocked cables may be connected incorrectly Step 2 Remove the faulty IVS1800 from the cabinet Step 3 Carry the device to the cabinet Ensure that the mounting ears at both sides of the device are tightly attached to the mounting bars in front of the cabinet Use one hand to hold the dev...

Page 291: ...xt Recommended tools and materials Phillips screwdriver ESD wrist strap or ESD gloves Procedure Step 1 Put on an ESD wrist strap or ESD gloves and insert the ground terminal into the ESD jack in the cabinet Step 2 Remove the faulty hard disk 1 Use a PH2 screwdriver to remove the two black screws on the rear of the chassis cover and take off the chassis cover Figure 6 19 Removing the chassis cover ...

Page 292: ...ith the opening of its locking buckle facing downwards hold the screw in the red framed part to lower the hard disk tray until it is level and fasten the black screws on the left and right sides and the white screw on the top Figure 6 22 Fastening the screw on the panel and the screws on the hard disk tray 3 Connect data and power cables to hard disks Connect hard disk cable ports P0 P3 to hard di...

Page 293: ...isk works abnormally contact Huawei technical support 6 4 3 9 Replacing a T H Sensor 33010516 Prerequisites A T H sensor needs to be replaced A spare T H sensor of the same model is available and functional Procedure Step 1 Tap Shutdown on the controller home screen NOTICE Exercise caution because the device is still energized after it is shut down on the controller home screen FusionModule500 Sma...

Page 294: ...r NOTE Before removing a T H sensor remember the DIP switch setting on it When you install a new T H sensor you need to set the same DIP switch setting for the new one End 6 4 3 10 Replacing a Smoke Detector Prerequisites Recommended tools and materials Phillips screwdriver insulation tape step ladder 2 m A smoke detector needs to be replaced A spare smoke detector of the same model is available a...

Page 295: ... Blow smoke toward the smoke detector using a smoke pistol until the smoke detector indicator changes from blinking once every 6s to steady on If a smoke detector fire alarm is triggered the smoke detector is functional End 6 4 3 11 Replacing a WLDS900 Water Sensor and Water Detection Rope Prerequisites Recommended tools and materials Phillips screwdriver crimping tool A water sensor needs to be r...

Page 296: ...gure 6 26 Water sensor components 1 Water detector 2 Conversion cable end A connected to the water detector 3 Conversion cable 4 Conversion cable end B connected to the water detection cable 5 Water detection cable end A connected to the conversion cable 6 Water detection cable Procedure Step 1 Replace the water detector 1 Remove the conversion cable at the conversion port for the water detector a...

Page 297: ...rring to the preceding steps 5 Connect the new water detector to the conversion cable Figure 6 28 Connecting a conversion cable to a water detector Step 2 Replace a water detection cable 1 Remove the faulty water detection cable from the port 2 Install a new water detection cable FusionModule500 Smart Mini Data Center User Manual 6 O M Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 287 ...

Page 298: ...ed If an alarm is generated the component is functional End 6 4 3 12 Replacing an Electrode Water Sensor Prerequisites Recommended tools and materials Phillips screwdriver crimping tool A water sensor needs to be replaced A spare water sensor is available Procedure Step 1 Disconnect the cable between the water sensor and the ECC800 Pro Step 2 Remove the faulty water sensor Step 3 Place the new wat...

Page 299: ...ude exceeds 1000 m Installation mode Installed on a concrete floor or an ESD floor Cable and pipe routing Pipes are routed from the top or bottom Input power cables of the cabinet can be routed in from the top or bottom and other power cables can be routed out from the top Signal cables can be routed out from the top or bottom Operating temperature Indoor 0 40 C Outdoor 20 C to 45 C Storage temper...

Page 300: ...a level 15ºC Table A 1 Derating coefficients of the UPS2000 G Altitude Unit m Derating Coefficients 1000 1 0 1500 0 95 2000 0 91 2500 0 86 3000 0 82 3500 0 78 4000 0 74 4500 0 7 5000 0 67 FusionModule500 Smart Mini Data Center User Manual A Equipment Derating Coefficients Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 290 ...

Page 301: ... Interface Module D DC direct current I IEC International Electrotechnical Commission M MCB miniature circuit breaker S SNMP Simple Network Management Protocol SPD surge protective device SOC State Of Charge SOH State Of Health U FusionModule500 Smart Mini Data Center User Manual B Acronyms and Abbreviations Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 291 ...

Page 302: ...UPS uninterruptible power system FusionModule500 Smart Mini Data Center User Manual B Acronyms and Abbreviations Issue 02 2020 12 25 Copyright Huawei Technologies Co Ltd 292 ...

Reviews: